Echoflex Installation Guide
Open Loop CCT Sensor
Range Confirmation
The Range Confirmation test quantifies the strength of the wireless signal
to a linked controller that has range confirmation capability.
Note:
Only one controller can be linked to the FLS-41 to run the
test properly. Disable repeaters that are in range.
1. Press and hold the
[Teach]
button until the green LED is displayed.
Release the button to enter the menu and display the first item, the
blinking green LED.
2. Press and release the
[Teach]
button to cycle through the menu of
color LEDs and stop when the blue LED is blinking.
3. Press and hold the
[Teach]
button until the LED stops blinking to
initiate the Range Confirmation test.
After the FLS-41 transmits and receives a Range Confirmation
message, the signal strength status is displayed as an LED blink color.
LED Blink
Signal Strength
Green
-41 to -70 dBm (best)
Blue
-70 to -80 dBm (good)
Red
-80 to -95 dBm (poor, move closer)
No LED
No linked controllers detected
The test repeats every five seconds and runs for 50 seconds. To exit
before the time-out, press and hold the
[Teach]
button.
Rapid Response Test
The Rapid Response Test confirms the settings on powered controllers to
which the FLS-41 is linked. The test accelerates the sensor's message rate,
making the controller respond to light level changes faster. The
transmission rate is increased to every 16 seconds for 100 seconds and
then returns to normal operation.
1. Press and hold the
[Teach]
button until the green LED is displayed.
Release the button to enter the menu and display the first item, the
blinking green LED.
2. Press and release the
[Teach]
button to cycle through the menu of
color LEDs and stop when the red LED is blinking.
3. Press and hold the
[Teach]
button to initiate the Rapid Response Test.
4. Vary the light level on the sensor to test the dimming and recovery
response of the connected light fixture.
5. To exit before time-out, press and hold the
[Teach]
button.