background image

Echoflex Installation Guide

Vacancy Sensor

6. Attach the sensor to the mounting plate by aligning the tabs on the

sensor with the slots on the mounting plate, and then twist clockwise
until the two are secured in place.

Soft Ceiling Tile Installation

EchoConnect and 

Ground wire pigtails 

optional

Ceiling tile

adapte

r

Terminate

 wires here

Ceiling tile

1. Pull the Belden 8471 (or equivalent) and 2.5 mm

2

(14 AWG) ) ground

wire to the mounting location and strip each wire to the appropriate
length. The strip length is dependent on the wire nut or other
termination connector used (wire nuts are not provided).

2. If you are installing the sensor in series with other sensors or

stations (continuing the data run), use the provided EchoConnect and
ESD ground wire pigtails. Termination connectors are not provided. If
you are not continuing the data run, direct termination to the
sensor controller is recommended, skip this step and proceed to
step 3.

a. Strip each wire to the appropriate length, depending on the wire

nut or other termination used (wire nuts are not provided).

b. Twist the incoming data - EchoConnect wire (typically black) and

the data - wire (black) from the EchoConnect pigtail as well as any
continuing data - EchoConnect wire together and secure with a
wire nut.

c. Repeat the above step for the data + EchoConnect wire (typically

white) and for the ESD ground wire (typically green/yellow), using
a new wire nut for each termination type.

Vacancy Sensor

Page 5 of 12

Echoflex

Summary of Contents for Elaho E-VAC-SR

Page 1: ...y Sensor provides 360 degree coverage of the installed location and is available in these models Model Coverage m 2 Coverage ft 2 E VAC SR Small Room 41 8 m 2 at 2 4 m 450 ft 2 at 8 ft 74 3 m 2 at 6 7...

Page 2: ...ght feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways glass partitions or adjacent rooms If the insta...

Page 3: ...t is provided with the Cat5 Termination Kit 8186A1207 for information to terminate Cat5 wiring Not all topologies are supported using Cat5 careful planning is required to ensure the proper termination...

Page 4: ...Connect pigtail as well as any continuing data EchoConnect wire together and secure with a wire nut c Repeat the above step for the data EchoConnect wire typically white and for the ESD ground wire ty...

Page 5: ...ensor in series with other sensors or stations continuing the data run use the provided EchoConnect and ESD ground wire pigtails Termination connectors are not provided If you are not continuing the d...

Page 6: ...and then bend each tine over in opposite directions for a secure fit on the unfinished side of the ceiling tile 5 Terminate EchoConnect and ESD ground wires to the terminal block on the sensor control...

Page 7: ...liary A buttons and their related LEDs are not used and have no functionality on the Responsive Vacancy Sensor Set Space and Address Two rotary switches on the sensor electronics provide for Space and...

Page 8: ...On all other local DIP switch settings are ignored Instead the settings made by the ElahoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4...

Page 9: ...ration is not allowed and no events are triggered Configuration Basic When the sensor is in Basic configuration mode DIP switch 2 set to Off the sensor will activate a Space Off command when vacancy i...

Page 10: ...ends the grace period begins When the sensor detects vacancy the vacancy timeout period begins If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a...

Page 11: ...tened to ten seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If aco...

Page 12: ...10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling...

Reviews: