Echoflex Installation Guide
Dual Tech Ceiling-mount Vacancy Sensor
Control Wire Specification
The sensor connects to the EchoConnect
®
communication bus. EchoConnect is
a bidirectional protocol that uses one pair of wires (data + and data -) for both
data and power. Echoflex recommends using Belden 8471 (or approved equal)
Class 2 wire. The total combined length of an EchoConnect wire run (using
Belden 8471, or equal) may not exceed 1,640 feet (500 m).
Note:
All control wiring should be installed and terminated by a
qualified installer and should follow standard wiring installation practices.
Leave approximately 8" (20 cm) of wiring in the back box for connection
and to allow slack for future service needs.
Note:
Echoflex requires that all Elaho stations and devices be grounded
for ESD protection. Pull an additional 14 AWG (2.5 mm
2
) wire for
grounding when control wires are not installed in grounded metal conduit.
Note:
When using Category 5 (or equivalent) cable on the EchoConnect
communication bus, please note the following:
•
Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kit and must be installed using a bus topology.
Refer to the installation guide that is provided with the Cat5
Termination Kit (8186A1207) for information to terminate
Cat5 wiring.
•
Not all topologies are supported using Cat5; careful planning
is required to ensure the proper termination kits are available
and the wire is pulled appropriately.
Parts and Supplies
The following parts and supplies are included with the sensor:
•
soft ceiling tile adapters
•
2 each screws, 6-32 x 3/4” and 1 3/4”
•
lens masks
•
WAGO connectors (wire termination connectors)
Dual Tech Ceiling-mount Vacancy Sensor
Page 3 of 12
Echoflex Solutions, Inc.