Prepare for Installation
Ceiling-mount sensors are intended for installation to a finished ceiling
surface, soft ceiling tile mounted, or attached to a round or octagonal fixture
junction box.
Compliance
•
UL/cUL listed, complies with UL508A, UL916, and CSA C22.2 No. 14
•
CE compliant
For use with Echoflex dimming and relay products.
Environment
Ambient
For indoor, commercial controls use only. Indoor installation only. The sensor
operates in ambient temperatures of -10°C to 40°C, with a maximum of
90% non-condensing humidity.
Installation
Echoflex recommends paying special attention to the installation
environment:
•
When operating in PIR only modes, the sensor must have an
unobstructed view of the room. Do not mount behind or near tall
cabinets, shelves, hanging light fixtures, etc.
•
Do not install the sensor within eight feet from an HVAC airflow
duct/vent.
•
Install the sensor where it cannot easily sense movement in areas
outside of the intended space, such as hallways, glass partitions, or
adjacent rooms. If the installation location cannot avoid these
conditions, portions of the lens can be masked to block the sensor
view of these undesired areas. See
Lens Masking on page 10
.
Note:
In areas of increased noise activity, enabling PIR only mode may
allow for better occupancy detection results. See
DIP Switch Settings on
page 7
.