Walk Test

The sensor offers a Walk Test mode, which shortens the vacancy timer to ten
seconds and allows for simple and quick verification of the sensor’s coverage
and range in the installed space.

[Walk Test]

1.

Prepare the site for configuration.

a.

Make certain the sensor and lighting loads are powered and
connected for control by the Elaho control system.

b.

You will need direct access to the sensor in order to place it into
Walk Test mode.

2.

Press the

[Walk Test]

button on the bottom of the sensor to enable

the Walk Test feature. A green LED will flash, indicating Walk Test is
enabled and the vacancy timer will be shortened to ten seconds.

3.

Move throughout the space including corners and areas that may be
obscured from line of sight to the sensor. Each time the sensor detects
movement, the lens illuminates red. If acoustic detection is enabled,
any sound detected will illuminate the lens green.

4.

Adjust the lens masking, if installed, blocking certain areas of the
installed space from sensor detection. See

Lens Masking below

.

5.

Walk Test mode automatically exits and the sensor returns to normal
operation after five minutes. You can also manually terminate by
pressing the

[Walk Test]

button again.

Lens Masking

Lens masks are provided in the packaging for your convenience. Use this to
block a section of the lens from detecting occupancy. To attach, cut to the
desired size, remove the backing and stick it on the sensor lens, covering the
desired sections.

Dual Tech Ceiling-mount Vacancy Sensor

Page 10 of 12

Echoflex Solutions, Inc.

Summary of Contents for Elaho Dual Tech Ceiling-mount Occupancy Sensor

Page 1: ...ctionality upon detection of vacancy The ceiling mount sensor offers 360 degree coverage with optimized lens options to accommodate small and large spaces The sensor is available in a white or black finish Small Room Lens coverage 452 ft 2 at 8 ft 42 m 2 at 2 4 m 804 ft 2 at 10 ft 74 3 m2 at 3 m Large Room Lens coverage 1 809 ft 2 at 8 ft 168 m 2 at 2 4 m 3 019 ft 2 at 10 ft 280 m 2 at 3 m Field i...

Page 2: ...ial attention to the installation environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not install the sensor within eight feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways gl...

Page 3: ... devices be grounded for ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cable on the EchoConnect communication bus please note the following Cat5 wiring must be terminated using EchoConnect Cat5 Termination Kit and must be installed using a bus topology Refer to the installa...

Page 4: ... location junction box or finished surface and strip each wire 3 8 9 10 mm 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor in one hand while gently twisting the cover clockwise 3 Connect the EchoConnect wires from the sensor to the installed wires a Connect the data typically black EchoConnect wire from sensor to the inco...

Page 5: ... hole for wire pass through b Remove the ceiling tile material from marked access hole c Pull the sensor wires through the access hole 4 Insert the soft ceiling tile adapters through the provided pinholes in the sensor mounting plate one set located on each side of the sensor near the mounting keyholes Push the adapters through the ceiling tiles then bend each tine over in opposite directions for ...

Page 6: ...unctionality on the Dual Tech Ceiling mount Vacancy Sensor DIP switches Space and Address switches Set Space and Address Two rotary switches on the controller provide for assignment of the sensor Space and Address By default these switches are set to Space 1 Address 1 Commands are shared by all devices within a given space 1 Set the Space rotary switch to the desired number 1 through 16 for the sp...

Page 7: ...re ignored Instead the settings made by the EchoAccess Mobile App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On and Switch 4 is Off Auto Both switches are On 5 Detection LEDs When set to On default the occupancy detection LEDs illuminate when movement is detected When set to Off the occupancy detection LEDs a...

Page 8: ...meout When the vacancy timeout in the space has only been reset by acoustic detection for 60 minutes acoustic detection is disabled until the next PIR detection event PIR only Detection When acoustic detection is disabled DIP switch 6 set to On the following logic is used When the space is vacant only manual control can switch the state to occupied When the space is occupied PIR detection and manu...

Page 9: ...ns If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period after a vacancy timeout occurs During this grace period if the sensor detects occupancy it will turn on or restore the previous lighting condition Auto Vacancy Timeout The Auto vacancy timeout setting va...

Page 10: ...n seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detection is enabled any sound detected will illuminate the lens green 4 Adjust the lens masking if installed blocking certain areas of the installed space from sensor detection See Lens Masking below 5 Wa...

Page 11: ...m 10 ft 3 0 m 10 ft 4 6 m 15 ft 4 6 m 15 ft 6 1 m 20 ft 6 1 m 20 ft 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft Dual Tech Ceiling mount Vacancy Sensor Page 11 of 12 Echoflex Solutions Inc ...

Page 12: ...Echoflex Installation Guide Dual Tech Ceiling mount Vacancy Sensor Dual Tech Ceiling mount Vacancy Sensor Page 12 of 12 Echoflex Solutions Inc ...

Reviews: