Echoflex Installation Guide

Elaho Vacancy Sensor

Junction Box Installation

Terminate

 wires here

1.

Pull the Belden 8471 (or
equivalent wire) and the
14 AWG (2.5 mm

2

ground wire

to the junction box.

2.

If you are installing the
sensor in series with other
sensors or stations
(continuing the data run), use
the provided EchoConnect
pigtail, ESD ground wire
pigtail. Termination connectors
are not provided. If you are
not continuing the data run,
proceed to Step 3.

a.

Strip each wire to the appropriate length, depending on the wire
nut or other termination used (wire nuts are not provided).

b.

Twist the data - (typically black) EchoConnect wire, the black
lead from the EchoConnect pigtail, and any continuing
EchoConnect (typically black) wire together and secure with a
wire nut.

c.

Repeat the above steps for the data + (typically white)
EchoConnect wire and the ESD ground wire.

3.

Orient the smooth side of the mounting plate to the junction box and
pull the EchoConnect wires (or terminated pigtail) from the junction
box through the provided holes near the center of the mounting plate.

4.

Secure the mounting plate to the junction box using the screws
provided (both short and long screws are provided for convenience).

5.

Strip each wire 5/16” (8 mm) and terminate the EchoConnect (white
and black wires) and the ground wire (green/yellow) to the
EchoConnect terminal block located on the sensor controller. Torque
each termination to 3.1-3.5 in-lb.

a.

Terminate the white incoming wire to the data + terminal.

b.

Terminate the black incoming wire to the data - terminal.

c.

Terminate the green/yellow (ground) wire to the ground terminal.

6.

Attach the sensor to the mounting plate by aligning the tabs on the
sensor with the slots on the mounting plate, then twist clockwise until
the two are secured into place.

Elaho Vacancy Sensor

Page 4 of 12

Echoflex Solutions, Inc.

Summary of Contents for E-VAC

Page 1: ...e coverage of the installed location and is available in three models E VAC SR Vacancy Sensor with small room lens covers 450 sq ft at 8 ft 800 sq ft at 10 ft E VAC Vacancy Sensor with standard room lens covers 1 800 sq ft at 8 ft 3 000 sq ft at 10 ft E VAC HC Vacancy Sensor with high ceiling lens covers 300 sq ft at 10 ft 7 000 sq ft at 40 ft Each sensor is available in white or black finish Lens...

Page 2: ...cable on the EchoConnect communication bus please note the following Cat5 wiring must be terminated using EchoConnect Cat5 Termination Kit and must be installed using a bus topology Refer to the installation guide that is provided with the Cat5 Termination Kit 8186A1207 for information to terminate Cat5 wiring Not all topologies are supported using Cat5 careful planning is required to ensure the p...

Page 3: ...ire pigtails 3 lens masks Note Follow all local code requirements for terminating wire Use appropriately sized wire nuts not provided to secure each termination The EchoConnect pigtail is only required when the sensor is installed in series with other stations or sensors If you are not continuing the data run direct termination on the control board is recommended Installation The Vacancy Sensor is...

Page 4: ...ite EchoConnect wire and the ESD ground wire 3 Orient the smooth side of the mounting plate to the junction box and pull the EchoConnect wires or terminated pigtail from the junction box through the provided holes near the center of the mounting plate 4 Secure the mounting plate to the junction box using the screws provided both short and long screws are provided for convenience 5 Strip each wire ...

Page 5: ...termination used b Twist the data typically black EchoConnect wire the black lead from the EchoConnect pigtail and any continuing EchoConnect typically black wire together and secure with the wire nut c Repeat the above steps for the data typically white EchoConnect wire and for the ESD ground wires 3 Create a hole for wire pass through in the ceiling tile by poking through the center hole or oblo...

Page 6: ...le using the rotary switches on the rear panel of the sensor Additional DIP switches and the Mode button also located on the rear panel set the sensor functionality and the occupancy detected action Set Space and Address Two rotary switches on the rear panel of the controller provide for assignment of the sensor Space and Address By default these switches are set to Space 1 Address 1 Commands are ...

Page 7: ...e App for Vacancy Timeout and Enable PIR LED are used DIP Switch 3 4 DIP switch 3 4 set the Vacancy Timeout to 5 15 30 minutes or Auto See Vacancy Timeout on the next page 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 Switch 3 is On and Switch 4 is Off Auto Both switches are On See Auto Vacancy Timeout on the next page DIP Switch 5 DIP switch 5 enables disable...

Page 8: ... reference the ElahoAccess Mobile App integrated help system Vacancy Timeout Vacancy timeout is the amount of time the sensor waits to take action after no movement is detected By default vacancy timeout is set to 15 minutes indicated by DIP switch 3 set to Off and 4 set to On When the vacancy timeout ends the grace period begins When the sensor detects vacancy the vacancy timeout period begins If...

Page 9: ...ts sensitivity to eliminate nuisance tripping When the sensor powers on the red PIR LED illuminates for approximately 60 seconds to identify Power Up state Sensor configuration is not allowed During this time no events are triggered Test Vacancy Sensors offer a Walk Test mode which shortens the vacancy timer to ten seconds allowing for simple and quick verification of the sensors coverage and rang...

Page 10: ...alk Test is enabled and the vacancy no vacancy occupancy timer will be shortened to ten seconds 3 Move throughout the space including corners and areas that may specifically be obscured from line of sight to the sensor Each time the sensor detects movement the lens will illuminate red 4 Adjust the lens masking if installed blocking certain areas of the installed space from sensor detection See Len...

Page 11: ...0 12 2m 40ft 9 1m 30ft 6 1m 20ft Small Room side view 0 0 1 5m 5ft 1 5m 5ft 3 0m 10ft 3 0m 10ft 4 6m 15ft 4 6m 15ft 6 1m 20ft 6 1m 20ft 8ft 2 4m 10ft 3 0m 12ft 3 7m Large Room side view 0 8ft 2 4m 10ft 3 0m 12ft 3 7m 0 3 0m 10ft 3 0m 10ft 6 1m 20ft 6 1m 20ft 9 1m 30ft 9 1m 30ft 12 2m 40ft 12 2m 40ft Elaho Vacancy Sensor Page 11 of 12 Echoflex Solutions Inc ...

Page 12: ...Echoflex Installation Guide Elaho Vacancy Sensor Elaho Vacancy Sensor Page 12 of 12 Echoflex Solutions Inc ...

Reviews: