Echoflex Installation Guide
Elaho Vacancy Sensor
6.
Strip each wire 5/16” (8 mm) and terminate the EchoConnect (white
and black wires) and ground wire (green/yellow) to the EchoConnect
terminal block located on the sensor control board. Torque each
termination to 3.1-3.5 in-lb.
a.
Terminate the white incoming wire to the data + terminal.
b.
Terminate the black incoming wire to the data - terminal.
c.
Terminate the green/yellow (ground) wire to the labeled ground
terminal.
Sensor Configuration
The Vacancy Sensor participates in an Elaho system using the configured
Space and Address, which are selectable using the rotary switches on the rear
panel of the sensor.
Additional DIP switches and the [Mode] button, also located on the rear
panel, set the sensor functionality and the occupancy detected action.
Set Space and Address
Two rotary switches on the rear panel of the controller provide for assignment
of the sensor Space and Address. By default, these switches are set to
Space
1,
Address
1. Commands are shared by all devices within a given space.
1.
Set the
Space
rotary switch to the desired number (1 through 16) for
the space you want the sensor to control.
2.
Set the
Address
rotary switch to desired address (1 through 16) for the
sensor identification in the selected space.
Note:
Do not duplicate a device Address within the same Space.
Elaho Vacancy Sensor
Page 6 of 12