2-4
Shipping Content and Hardware
Echelon's 72901 Power Supply includes a compatible 2.1mm barrel connector. Should a
different power supply be used, ensure that the barrel connector meets the following
specifications: ID=2.1mm, OD=5.5mm, L=11mm.
A black
,
two-position Weidmüller (PN 125911) BL screw terminal connector is also provided
for those preferring to use screw connections. This screw terminal will accommodate wire
gauges from 24AWG/0.5mm to 12AWG/2mm: ensure that the selected wire gauge can deliver
the voltage and current required by the
i.
LON 1000, taking into account any voltage drop
created by wire resistance.
Twisted Pair L
ON
W
ORKS
Network Connection
An orange
,
two-position Weidmüller PN 148426 BLAT screw terminal connector is provided
for connection to the L
ON
W
ORKS
twisted-pair channel. The
i.
LON 1000 model 72001 supports
the TP/FT-10 free topology channel, while model 72002 supports the TP/XF-1250 channel.
Suitable cables for L
ON
W
ORKS
channels are listed in Echelon’s engineering bulletin,
Junction Box and Wiring Guidelines
, part number 005-0023-01 (available from Echelon's
web site at www.echelon.com).
!
Use ONLY cables that are listed in this bulletin. The use
of unsuitable cables will result in improper network
communications.
!
Ensure that the L
ON
W
ORKS
network is correctly terminated.
!
TCP/IP Connection
The
i.
LON 1000 connects to any TCP/IP network via the integral 10BaseT Ethernet port.
A
standard category 5 Ethernet cable (provided) must be used to connect the i.LON 1000 to a
10BaseT hub.
Console and Serial EIA-232 Ports
The console port is used to configure the
i.
LON 1000, and provides a serial connection to a
VT-100 terminal or terminal emulation software such as HyperTerminal; the serial port is
reserved for future use. The format of the console port data is 9600 baud, 8 data bits, 1 stop
bit, no parity, and no flow control.
A null-modem cable (provided) is required between the
i.LON 1000 and the communication port of the PC used for configuration
.
The cable connection of a null-modem cable is shown in Figure 2-2.