EXCEL 50 INSTALLATION INSTRUCTIONS
35
EN1B-0101
START-UP SEQUENCE
After powering up the controller or after a RESET the initial
screen of the Start-up sequence appears. A RESET can be
achieved by pressing the 'DOWN' and '–' keys simul-
taneously.
NOTE:
The screens of the Start-up sequence are always
displayed in English as they are a part of the
operating system.
NOTE:
The sequence shown is for embedded applications.
The Start-up sequence for standard and custom
CARE applications is similar but does not include
entry of configuration codes. See the Excel 50 User
Guide, EN2B-137, for more details.
Honeywell
XL 50
V 2.04.00
>
NEXT
This is the first screen of the Start-up sequence. It shows the
version of the company name, the controller name and the
firmware version. Confirm with ENTER.
Date:
>
13.06.1998
Time:
>
17:35
Ctr
No:
>
1
>
NEXT
Select:
—
the 'Date' field to enter the current date.
—
the 'Time' field to enter the current time.
—
the 'Ctr. No' field to enter the controller number.
Confirm with ENTER.
If 'Date' is selected:
Set the date using the '+' or '–' keys. Use the arrow keys to
move from field to field. Confirm with ENTER. Select BACK.
Confirm with ENTER to return to the previous screen.
NOTE:
The date must be entered in the following format:
DD. MM. YYYY; for example, the 23
rd
of July 1997
must be entered as 23. 07. 1997. Press the
CANCEL key to abort the operation or to cancel an
incorrect entry before ENTER has been pressed.
The value previously displayed will be restored.
If 'Time' is selected:
Set the time using the '+' or '–' keys. Use the arrow keys to
move from field to field. Confirm with ENTER. Use the
CANCEL key to return to the previous screen.
NOTE:
The time must be entered in the following format:
HH:MM in 24 hour clock format; for example: 9:30
a.m. must be 09:30 and 9:30 p.m. must be 21:30.
Press the CANCEL key to abort the operation or to
cancel an incorrect entry before ENTER has been
pressed. The value previously displayed will be
restored.
If 'Ctr. No.' is selected:
Set the controller number using the '+' or '–' keys. Confirm
with ENTER.
IMPORTANT
If no controller number is set or if the number shown
is not reconfirmed, the controller will not go online on
the C-Bus after start-up.
Move the cursor to the 'NEXT' field with the ARROW keys.
Confirm with ENTER.
Modem Part:
<
active/inactive
>
Appl. Mem. Size
128 KB .
>
NEXT
This screen provides information about whether modem com-
munication is enabled and about application memory size.
Enabling modem communication and changing the value for
application memory are done in a later screen. NEXT is high-
lighted. Confirm with ENTER.
>
Contr. Setup
>
Select Applic.
>
Requ. Download
>
DP Wiring Check
Select:
—
'Contr. Setup’ to configure the controller-specific
hardware interfaces.
—
'Select Applic.' to choose the application manually.
—
'Requ. Download' to download an application via the
XI584 PC MMI or the C-Bus.
—
'DP Wiring Check’ to set up the test mode with default
user addresses.
Confirm with ENTER.
Controller Setup
If 'Contr. Setup.' has been selected, the following screen will
appear:
HW-Interf. Cfg.
>
B-Port
↑
C-Bus
1
LON-Bus
↓