EXCEL 50 INSTALLATION INSTRUCTIONS
EN1B-0101
34
Fig. 60. PW3 Meter Adapter power connections.
Meter-Bus activity can by monitored using the LEDs on the
HE01 application module (see Fig. 61).
C-BUS
METER BUS
(RJ45 JACK)
LEDs
SHI
E
LD
C + C -
C-BUS TxD, YEL
POWER, GRN
C-BUS RxD, YEL
METER BUS TxD, YEL
METER BUS RxD, YEL
00
00
012
3
4 5 6
C-BUS
TERMINATION
SWITCH
Fig. 61. XD50-FCS Application Module LEDs.
Table 26. Meter bus devices supported
Device
Baud-
rates
Mode
Energy
Vol.
Pwr. Flow Fwd.
Temp.
Ret.
Temp.
Temp.
Diff.
Energy at
Ref. Day
Ref.
Day
300
2400
1
normal
X
X
X
X
X
X
X
X
Siemens
2WR4
300
2400
2
fast
X
X
X
X
X
X
300
2400
1
normal
X
X
X
X
X
X
X
Schlumberger
CF50
300
2400
2
ref. day
X
Landis & Staefa
Sonogyr WSD
300
1
X
X
X
X
X
X
X
X
Techem
Delta-tech
Kompact and Split
300
2400
1
X
X
X
X
X
X
ABB / SVM
SVM 840
300
2400
1
X
X
X
X
X
X
X
Raab Karcher
Sensonic
300
2400
1
X
X
X
X
X
X
X
Kamstrup
Multical 3
300
2400
1
X
X
X
X
X
X
X
X
Zenner Multidata S1
4
2400
1
X
X
X
X
X
X
X
X
1
X
1
DZG Elektro
Baureihe S30 /
DVS3016
300
2400
9600
1
X
Relay
PadPuls M1C
300
2400
1
X
2
X
2
Relay
PadPuls M4L
300
2400
1
X
2
X
X
3
X
1) Storage number 8.
2) PadPuls must be configured. Only one value can be counted.
3) Energy or volume at reference day depends on PadPuls configuration.
4) The Zenner meter requires twice as much power as other meters. Thus, only 1 Zenner meter can be connected to the PW3.