TDS-100M Ultrasonic Flowmeter 

 

User Manual

Ver.18.0

 

Summary of Contents for TDS-100M

Page 1: ...TDS 100M Manual 1 TDS 100M Ultrasonic Flowmeter User Manual Ver 18 0...

Page 2: ...DS 100M Manual 2 ground line include upstream ground line and downstream ground line CONTENT 1 Must knows about TDS 100M 5 2 Introduction to TDS 100M 6 3 Menu Window Details 7 4 transducersinstallatio...

Page 3: ...e software the parameters that TDS 100M needs to work properly could be downloaded by use of the RS232 port on the PC If your computer does not have a RS232 port you need to buy a USB RS232 converter...

Page 4: ...y located on Menu 48 which shows the points of lines for the linearity correction function 0 stands for shutting off the function The default value is 0 Try to make sure that value is 0 so as to avoid...

Page 5: ...RS232 and RS485 serial port 4 One or two analog inputs 5 Optional 4 20mA analog output 6 Two OCT output channels 7 Ability to measure sew water 8 4 kinds of different types of transducers can be used...

Page 6: ...ate positive totalizer adjust the units in M30 M32 03 display instant flow rate negative totalizer adjust the units in M30 M32 04 display instant flow rate date time 05 display heat flow rate total he...

Page 7: ...is 8 seconds when inputing accures displaying according to the inputing operation when there is no inputing operation it will automatically enter cycle displaying status detailed information in 3 1 4...

Page 8: ...64 analogue input AI3 65 Analogue input AI4 66 Analogue input AI5 By inputing measuring range the flow meter will turn current signal into data range users need so display related analogue input that...

Page 9: ...play the Reynolds number and the pipe coefficient diagn osis 95 Display positive negative heat quantity totaliser start cycle display function 0 Display the time of power on off and flow rate 1 Displa...

Page 10: ...interference function little signal consumable ensure the device work well in longer term so the special signal cable supplied by factory is the best choice for you if using coaxial shielded radio fre...

Page 11: ...perature and pressure on the installation point should be within the work ability of the transducers 6 Pay more attention to the pipe scaling in inner pipe wall do best to choose the pipe without scal...

Page 12: ...east above 550mm width is more than D 550 2 mm cement pipe width is more than D 700 2 mm instrument well axial width L is more than D 1200mm when installing transducers avoid the place of flange weldi...

Page 13: ...ucer installation method Before installation choose density pipe to install transducers and clean the installation area clear away rust paint anti rust layer it is the best to use angle grinder to pol...

Page 14: ...llation method convenient to use with precise measurement when installation the two transducers horizontally align its centre line is horizontal with pipe axis line suitable pipe diameter range to mea...

Page 15: ...directly Insertion B type for sement pipe Suitable diameter Above DN80mm Above DN80mm Installation room 550mm 700mm Fluid temperature 40 160 40 160 Transducer material 316L stainless steel 316L stainl...

Page 16: ...between the vertical side of the fixed position paper and the extended line is A D Starting from A and along the edge of the position paper the length of half of the pipe perimeter is measured and th...

Page 17: ...ll valves have been welded on the hoops These hoops are directly fixed on the pipe and make sure that the centers of the ball valves overlap A and B respectively Finally the ball valves should be clos...

Page 18: ...seal the connection place 4 6 8 Length calculation of the part of transducer into the pipe inner wall Insertion style transducer is made of stainless steel by casting As the transducer s length A and...

Page 19: ...s of the two transducers are face to face that is the holes for wires are in the same direction and either upward or downward 5 After the transducer is installed the screw mut should be screwed tightl...

Page 20: ...14 20 360 105 75 55 2 14 4 16 25 390 115 85 65 3 14 4 16 32 450 140 100 76 3 18 4 18 40 2 5 500 150 110 84 3 18 4 20 50 200 160 125 100 3 18 4 22 65 200 180 145 120 3 18 4 24 80 225 195 160 135 3 18...

Page 21: ...l quality is indicated as the Q value display on M90 that represent the receiving signal is good or not TDS 100M series use 00 99 digits to represent signal quality 00 represent the worst signal 99 re...

Page 22: ...r environment electromagnetic interference or lower receiving signal then the flow rate displayed is poor not be able to work normaly for long time 4 after installation enter M26 to solidify parameter...

Page 23: ...le to receive signal Loosen contact or not enough couplant between transducer and pipe surface Transducers installed improperly scaling on inner pipe wall is too thick new changed liner Make sure the...

Page 24: ...K Empty pipe setup in M29 no liquid in pipe or wrong setup if there is liquid actually input 0 value in M29 Attention the codes of Q E displayed do not affect measurement only means current loop and...

Page 25: ...trument A quotation will be sent to the customer before proceeding with the service 6 3 Software Upgrade Service We provide free of charge software upgrade services Please contact the factory for any...