PLEASE NOTE: SH22 IS FOR OUTDOOR PERMANENT INSTALLATIONS ONLY AND SH22I IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL
AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT NOTICE. PLEASE VISIT SUPPORT.ECCOTEMP.COM FOR MORE INFORMATION.
Support:
Support.Eccotemp.com
Shop Online:
www.Eccotemp.com
Phone:
866-356-1992
Installing the SH22i Water Heater, Continued...
US Installations1
Canadian Installations2
A =
Clearance above grade,
veranda, porch, deck,
or balcony
12 in (30 cm)
12 in (30 cm)
B = Clearance to window or
door that may be opened
4 ft (1.2 m) below or to
side of opening; 1 ft (300
mm) above opening
6 in (15 cm) for
appliances ≤ 10,000 BTUH
(3 kW), 12 in (30 cm) for
appliances > 10,000 BTUH
(3 kW) and ≤ 100,000
BTUH (30 kW), 36 in
(91 cm) for appliance >
100,000 BTUH (30 kW)
C = Clearance to permanently
closed window
*
D = Vertical clearance to
ventilated soffit located
above the terminal
within a horizontal
distance of 2 feet (61 cm)
from the center line of
the terminal
*
E =
Clearance to unventilated
soffit
*
Clearance above grade,
veranda, porch, deck,
or balcony
12 in (30 cm)
12 in (30 cm)
Clearance to window or
door that may be opened
4 ft (1.2 m) below or to
side of opening; 1 ft (300
mm) above opening
6 in (15 cm) for
appliances ≤ 10,000 BTUH
(3 kW), 12 in (30 cm) for
appliances > 10,000 BTUH
(3 kW) and ≤ 100,000
BTUH (30 kW), 36 in
(91 cm) for appliance >
100,000 BTUH (30 kW)
Clearance to permanently
closed window
Vertical clearance to
ventilated soffit located
above the terminal
within a horizontal
distance of 2 feet (61 cm)
from the center line of
the terminal
Clearance to unventilated
soffit