Subject
Descrip
�
on
Part's Function
It is the component on which the gas + air mixture exits and on
which flame is formed.
Impact in Case of
Malfunction
1- Irregularity in the boiler emissions
2- Explosive burning
3- Flame loss
Main Associated Error
Codes
E01, E82, "Flame Loss Risk" warning
Diagnostics and Test
Method
Visual Control: Closed hole on the burner, oxidation,
deformation, etc. cleaning with a non-metallic brush.
• Burner
Table
12
63