ENTERING THE HISTORY MENU
You can see the device data in this menu during operation in the following order.
7.
ERROR CODES (DEFINITIONS-SOLUTIONS) AND PREDICTIVE MAINTENANCE
WARNINGS
1. Number of Hours with Main Power Supply ON (total
number of hours with main power supply ON)
2. Error history (last 8 errors)
3. Number of Burner Switching (total number of burner
switching)
4. Number of CH Burner Switching (total number of CH
burner switching)
5. Number of DHW Burner Switching (total number of
DHW burner switching)
6. Number of CH Hours of Operation
7. Number of DHW Hours of Operation
8. Number of Burner OFF Hours
9. Number of Pump ON Hours of Operation
10. Number of Flame Loss Predictions
Error Code
Error Type
Probable Cause
Solution
E01
Ignition Failure
No gas supply to the
boiler.
1-
Ensure that the gas valve is on.
2- Ensure that there is gas supply.
3- If the gas valve is off, turn it on and press the reset button.
4- Check the gas setting. If there is a problem, adjust the gas setting according to the table given in
the manual and reset the device.
5- Check fan-venturi-silencer assemblies.
6- Check if the siphon is clogged. Ensure that the connection is slopping at least 3° downwards and
there is water in the main heat exchanger up to the part where the electrode is located.
7- If the siphon is clogged, clean it. If there is a problem with the gland, replace it. If the electrode is
wet, replace it. Then reset the device.
8- Ensure that the connection of the electrode cable (both on the mainboard and on the main heat
exchanger) is done correctly and that it sits properly. If there is a problem, make sure it is properly
installed and locked. Then reset the device.
9- Check the cable connections and ensure the cables are not damaged. If there is damage, replace
them and reset the device.
10- If the problem persists, remove the ignition electrode and check for oxidation. If there is oxidation,
clean the electrode and place it back and then reset the device.
11- Check the distance of the ignition and ionization electrodes. If there is a problem, adjust it
according to the measurements given in the manual. Then reset the device.
12- Turn off the boiler and check for a resistance of 110-120 ohm between the ends of the gas valve.
If the resistance value is not within this range, replace the gas valve.
13- Remove the gas valve connector and turn on the boiler's electrical connection. Ensure that there
is a voltage of 23-25 V between the ends of the connector from the mainboard during ignition. If it is
not in this range, replace the mainboard.
Figure 7
12
Summary of Contents for CONFEO PREMIX P 14 HM
Page 1: ...SERVICE MANUAL CONFEO PREMIX CONDENSING BOILER CONFEO PREMIX P 14 20 24 28 30 35 HM HCH HST...
Page 24: ...12 ELECTRICAL DIAGRAM Figure 15 24...
Page 34: ...Low Voltage Removing installing the pump cable FAN PWM CABLE Figure 39 Figure 40 34...
Page 52: ...Figure 76 Figure 77 52...
Page 83: ......