(1) Network disconnection recovery time: When the network disconnection recovery time is set to ≥20 seconds. After the
connection between the sending end and the receiving end is disconnected, if the network is still disconnected after a
long delay, the receiving end will output a disconnected switch signal.
Note: When the user uses, the default parameters cannot meet the requirements of the environment and the site, the user
needs to debug and write the appropriate time, and determine the appropriate network disconnection recovery time value
by observing the "NET" connection indicator of the product. In case of engineering application, the disconnection of the
network will cause the receiving end to output a disconnected digital signal or maintain the output value before the
disconnection, thus affecting the instability or malfunction of the system!
Parameter
name
Scope and Options
Illustrate
Sender: network
disconnection
recovery time
(K61-40)
0 seconds
Turn off disconnection recovery. The receiving end keeps the
output value before the disconnection, until the network connection
returns to normal, or the initial value is restored by artificial power
failure.
20 seconds to 57600 seconds
(default 20 seconds)
Enable disconnection recovery. That is, after the disconnection time
is exceeded, the receiving end outputs the disconnected switch
signal.
Receiver:
disconnection
recovery
time:
(K61-04)
0 seconds
Turn off disconnection recovery. The receiving end keeps the
output value before the disconnection, until the network connection
returns to normal, or the initial value is restored by artificial power
failure.
60 seconds to 57600 seconds
(default 60 seconds)
Enable disconnection recovery. That is, after the disconnection time
is exceeded, the receiving end outputs the disconnected switch
signal.
Example: The network disconnection recovery time is set to: 20 seconds. After the sender and receiver are disconnected,
the product will continue to search for connections. If the connection between the sending end and the receiving end is
still disconnected after 20 seconds, the product network indicator "NET" light is off, and the receiving end returns to the
default output and outputs a disconnected digital signal.
(2) DO digital output: the output state of the output terminal.
Parameter name
Scope and Options
Illustrate
DO digital output
Mutual transmission
When the sending end is closed, the receiving end is
closed, and when the sending end is disconnected, the
receiving end is disconnected.
Mutual self-lock
The sending end is closed and disconnected once, and
the state of the receiving end changes once (closed to
open, open to closed)
Time off
The sending end is closed and disconnected, and the
receiving end waits for a certain time to close, the
default is 1S, the range (1~5000S)