Temporary lock may be deactivated by SMS or GRPS command (RLIMIT command)
7.3.2.
Outputs
7.3.2.1.
Activation mode and timing
Thanks to this option you may choose output operation mode. There are two
operation modes available:
o
Bistable- connection follows for indefinite time- up to the moment of
disconnection of power for module or remote command which switches
output off,
o
Monostable- connection follows for time defined by user - every 100ms.
7.3.2.2.
Conditions
Defines conditions for activating both of outputs. User can set following conditions:
•
No connection to server (immediately after detection);
•
No GSM signal (immediately after detection);
•
Detection of incoming call from defined telephone number;
•
Dependent on state transitions from non-active to active of one of the
inputs. Outputs can be also activated by internal watchdog (see 7.7
LINK
CONTROL
).