Operating instructions

P2E076-AC06-01

Translation of the original operating instructions

4.5 Checking the connections

;

Make sure that the power is off (all phases).

;

Secure it from being switched on again.

;

Check the correct fit of the connection lines.

4.6 Switch on device

;

Inspect the device for visible external damage and the proper function
of the protective features before switching it on.

;

Apply the nominal voltage to the voltage supply.

4.7 Switching off the device

;

Disconnect the device from the supply voltage at the main switch for
the supply line.

;

When disconnecting, be sure to disconnect the earth wire connection
last.

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not carry out any repairs.
Return the pump to the manufacturer for repair/replacement.

CAUTION
Electrical load on the capacitor after device is switched off

Electric shock, risk of injury
→ Discharge the capacitors before working on the device.

CAUTION
The motor restarts automatically when operating voltage
is applied, e.g. after a power failure.

Danger of injury
→ When working on the pump, switch off the mains supply

voltage and secure the latter from being switched on again.

→ Wait until the pump stops.

If the device remains out of use for some time, e.g. when in
storage, we recommend switching the device on for at least
two hours to allow any condensate to evaporate and to move
the bearings.

Malfunction/error

Possible cause

Possible remedy

Impeller running
roughly

Imbalance in rotating
parts

Clean the device; if
imbalance is still
evident after
cleaning, replace the
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply
voltage faulty

Check mains supply
voltage,
restore power
supply.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Thermal overload
protector responded

Allow motor to cool
off, locate and rectify
cause of error, if
necessary cancel
restart lock-out

Unacceptable
operating point

Check operating point

Overtemperature of
motor

Ambient temperature
too high

Lower ambient
temperature if possible

Insufficient cooling

Improve cooling

Item no. 10615-5-9970 · Revision 68158 · Release 2010-11-29 · Page 8 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for P2E076-AC06-01

Page 1: ...he electrical system Only trained and authorised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules...

Page 2: ...be ejected resulting in bodily harm Take appropriate safety measures 1 7 Emission WARNING Depending on the installation and operating conditions a sound pressure level greater than 70 dB A may arise...

Page 3: ...5 Transport and storage conditions and chapter 3 2 Nominal data Minding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards...

Page 4: ...Product drawing All measures have the unit mm 1 Connection line silicone 4G 4x brass lead tips crimped Item no 10615 5 9970 Revision 68158 Release 2010 11 29 Page 4 9 ebm papst Mulfingen GmbH Co KG B...

Page 5: ...e discharge holes None Operation mode S1 Motor bearing Ball bearing Touch current acc IEC 60990 measuring network Fig 4 TN system 0 75 mA Motor protection Thermal overload protector TOP wired internal...

Page 6: ...e Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether t...

Page 7: ...tructions 4 4 Connection screen U1 blue Z brown U2 black PE green yellow Item no 10615 5 9970 Revision 68158 Release 2010 11 29 Page 7 9 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Ph...

Page 8: ...and secure the latter from being switched on again Wait until the pump stops If the device remains out of use for some time e g when in storage we recommend switching the device on for at least two ho...

Page 9: ...sual inspection At least every 6 months Replace device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At least...

Reviews: