Operating instructions

K3G400-AQ23-90

`

II 2G Ex d e ib IIB T3 Gb

IBExU14ATEX1122 X /01

`

Translation of the original operating instructions

54003-4-8670

Fans installed in upright position

When routing the cable, ensure that the screwed cable glands are
arranged at the bottom. The cables must always be routed downwards.

Fig. 8: Cable routing for fans installed upright.

5.4 Factory settings

Factory settings with which the device is pre-set by ebm-papst.

Control mode
parameter set 1

PWM controlling

Control mode
parameter set 2

PWM controlling

Fan / device adress

01

Max. PWM / %

100

Min. PWM / %

5

Save set value to
EEPROM

Yes

Set value control

Analogue (linear)

Control function
parameter set 1

Positive (heating)

Control function
parameter set 2

Positive (heating)

Item no. 54003-5-9970 · ENG · Revision 90396 · Release 2016-09-21 · Page 12 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G400-AQ23-90

Page 1: ...ions are available in other languages on our website www ebmpapst com 2 2 SAFETY REGULATIONS AND NOTES 2 2 1 Levels of hazard warnings 2 2 2 Staff qualification 2 2 3 Basic safety rules 2 2 4 Electric...

Page 2: ...efects which impair safety must be rectified immediately Do not make any modifications additions or conversions to the device such as modifying the guard grille or attaching other equipment to the wal...

Page 3: ...el greater than 70 dB A may arise Danger of noise induced hearing loss Take appropriate technical safety measures Protect operating personnel with appropriate safety equipment e g hearing protection A...

Page 4: ...IIA and IIB and temperature classes T1 to T3 Using the device only in stationary systems Using the device only in resonance free speed ranges to avoid spark formation Punctual complete performance of...

Page 5: ...min 10 mm max 14 mm tightening torque 6 0 6 Nm standard value depending on cable 6 Attachment screws for terminal box cover tightening torque 3 5 0 5 Nm 7 Earth connection point M8 functional earth t...

Page 6: ...display Input for sensor 0 10 V or 4 20 mA External 24 V input programming External release input Alarm relay Integrated PID controller Motor current limit PFC passive RS485 MODBUS RTU Soft start Cont...

Page 7: ...l number Ex identification II 2 G Ex d e ib IIB T3 Gb Element Explanation Ex marking according to 2014 34 EU II Device group II use above ground not mining 2 Category 2 Zone 1 Category 3 Zone 2 G Ex a...

Page 8: ...may not introduce any forces into the device that place stress on the frame structure and that affect the Ex relevant gap e g uneven mounting level air duct connections or the like During installation...

Page 9: ...the terminal box from ebm papst have been inspected for their suitability The motor must be connected in accordance with EN 60079 14 Earth wire contact resistance to EN 61800 5 1 Compliance with the i...

Page 10: ...cting cables with terminals Open the terminal box To do so unscrew the seven attachment screws for tightening torque see chapter 4 1 Product drawing Take care when opening the terminal box cover Do no...

Page 11: ...onnections and cable glands have been tightened to the specified torque 5 3 3 1 Exchange of screwed cable glands and plug screws If you would like to replace screwed cable glands or plug screws for ex...

Page 12: ...tings Factory settings with which the device is pre set by ebm papst Control mode parameter set 1 PWM controlling Control mode parameter set 2 PWM controlling Fan device adress 01 Max PWM 100 Min PWM...

Page 13: ...current motor level control coefficient motor speed parametrisable curve SELV 2 Din 2 Digital input 2 Parameter set 1 2 switching depending on EEPROM setting the valid used parameter set can be select...

Page 14: ...L2 L3 and PE are short circuited outside the potentially explosive area e g on the main switch Disconnect the connection line on the device When disconnecting be sure to disconnect the earth wire conn...

Page 15: ...load back pressure too high Correct the operating point Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it on again Alternatively r...

Page 16: ...l check by turning the rotor whilst switched off vibration test At least every 3 months Replace the device in the event of noise stiffness or bearing play Have the motor bearings replaced by ebm papst...