Appendix
8.1 Technical data
Applies only to XV-3.3-..-.E.-...-.. XV300 units with aSmartWire-DT
®
connection.
Supply voltage U
Aux
Rated operating voltage
24 V DC
Effective: 20.4-28.8 V DC (rated operating voltage -15/+20%)
Residual ripple of input voltage
max. 5%
Protection against polarity reversal
yes
max. current
max. 3A
Notes
If contactors with a total current consumption > 3 A (for accept-
ance by UL: 2A) are connected, a power feeder module EU5C-
SWD-PF1 or EU5C-SWD-PF2 has to be used.
Short-circuit strength
no, external protection necessary with fuse FAZ Z3
Potential isolation
no
Heat dissipation
Normally 1.0 W
Rated operating voltage of 24-V
DC
mod-
ules
Normally U
Aux
- 0.2 V
SmartWire-DT
®
supply voltage U
Pow
Specifications for connection to supply
voltage
24 V DC
Effective: 20.4-28.8 V DC (rated operating voltage -15/+20%)
Residual ripple of input voltage
max. 5%
Protection against polarity reversal
yes
Rated operational current
max. 0.7 A
Overload proof
yes
Inrush current and length
12.5 A/6 ms
Heat dissipation at 24 V DC
1.0 W
Bridging voltage dips
10 ms
Repetition rate
1s
status display
LED
XV300
12/15 MN048017 EN www.eaton.eu
83