5 Installation
5.4 Mounting
HMI/PLC XV-102
08/2016 MN04802004Z-EN
www.eaton.com
51
5.4
Mounting
1
Check the device for transit damage.
2
Mount the device in the control cabinet, control panel or the control desk. See chapter 5.4.1
Mounting the device,
3
Connect the device as required for your application.
Follow the instructions on wiring the relevant interface. See chapter 5.3 Interfaces,
CAUTION
Interference
The values specified in the technical data and the device's electromagnetic compat-
ibility (EMC) cannot be guaranteed if unsuitable cables, improperly assembled and
terminated cables, and/or unprofessional wiring are used.
Only use cables prefabricated and terminated by professionals.
The cables being used must be assembled and terminated as required by the
port/interface description in this document.
When wiring the device, follow all instructions regarding how to wire the corre-
sponding port/interface.
All general Directives and standards must be complied with.
CAUTION
Condensation in/on the device
If the device is or was exposed to climatic changes (temperature fluctuation, air hu-
midity) moisture can form on or in the device (device condensation). In this case,
there is a risk of short-circuit.
The device must
not
be switched on when device condensation is present.
If the device has condensation in or on it, or if the device has been exposed to
temperature fluctuations, let the device settle into the existing ambient air tem-
perature before switching it on (do not expose the device to direct thermal radia-
tion from heating appliances).
The device must only be installed and commissioned in perfect technical condition and
in compliance with this document.
The device does not have an ON/OFF switch. The device is not provided with an On/Off
switch. If the power supply is not provided with a switch, the device will start up (boot)
as soon as it is connected to the power supply.