Configuration check
Each time the supply voltage is switched on, the configuration checks are performed:
1
The slaves actually found on the network are compared with the target configuration stored in the
device.
If the physical structure of the SmartWire-DT network matches the target configuration, the
SmartWire-DT network is ready for data exchange.
2
The target configuration stored in the device is compared with the project configuration defined in
the PLC.
If the target configuration matches the project configuration, the Config LED lights up.
Tab. 16 SWD-LED and Config LED
LED
State
Meaning
Smart-
Wire-DT
Off
No target configuration present.
Continuous red light
Short-circuit on the 15 V DC power supply.
No SmartWire-DT module found.
Red flashing
The modules found in the SmartWire-DT network do not match the
target configuration.
A SmartWire-DT module configured as necessary is missing.
Orange flashing
The physical configuration of the SmartWire-DT network is read in and
stored in the device as the target configuration.
Green flashing
The physical configuration of the SmartWire-DT network is com-
pared with the target configuration.
The SmartWire-DT modules are addressed.
Continuous green
light
The modules found in the SmartWire-DT network match the target
configuration. The SmartWire-DT network is ready for data exchange.
Config Off
No project configuration present.
Faulty target configuration (see SWD-LED).
Continuous red light The project configuration and the stored target configuration are not
compatible.
Green flashing
The project configuration is compatible with the stored target configura-
tion.
Continuous green
light
The project configuration is identical to the stored target configuration.
The description of the project configuration (SmartWire-DT configuration in XSoft-COD-
ESYS project) are provided in the Document «User Manual XSOFT-CODESYS 2
MN04802091Z, PLC programming» or «User Manual XSOFT-CODESYS 3 MN048008ZU,
PLC programming», Chapter «SmartWire-DT configuration».