Eaton xComfort F94 Series Assembly Instructions Manual Download Page 4

4

Eaton RF System Basic Mode Quick Reference 

Symbols: 

 

       

 

 

Sensors: 

  

 

 

 

 

Actuators: 

   Link Device       

 Unlink Device (selectively) 

  Reset actuator (all settings & connections)   

  Manual Operation 

 LED is on

 LED flashes 5 times 

 LED is on 

 Lamp (LED) is on  

 Lamp (LED) is on 

1. Link devices 

Assign a pushbutton to an actuator

1. Press the configuration pushbutton with a screwdriver 
    for less than 0.5 sec => actuator enters teach-in mode  
    the LED in the actuator is on 
2. Press the selected pushbutton for less than 0.5 sec  
3. LED in the actuator flashes twice for confirmation  
4. Press the configuration pushbutton with a screwdriver for less than 0.5 sec => actuator leaves teach-in mode 

Assign a remote control to an actuator 

1. Press the configuration pushbutton with a screwdriver 
   for less than 0.5 sec => actuator enters teach-in mode,     
   the LED in the actuator is on 
2. Press the selected remote push button for less than 0.5 sec 
3. The LED in the actuator flashes twice for confirmation  
4. Press the configuration pushbutton with a screwdriver for less than 0.5 sec => actuator leaves teach-in mode 

Assign a room thermostat to an actuator

1. Press the configuration pushbutton with a  
    screwdriver for less than 0.5 sec => actuator 
    enters teach-in mode,  the LED in the actuator is on 
2. Turn the control knob to +  
3. The LED in the actuator flashes twice for confirmation  
4. Press the configuration pushbutton with a screwdriver for less than 0.5 sec => actuator leaves teach-in mode 

Assign a channel of the binary input in 
switch mode

1. Press the configuration button on the binary 
    input (the mains supplied version requires a screwdriver) for selecting the mode, switch mode is Mode 2, LED 
    flashes 2x for Mode 2  
2. Open contact of the binary input  
3. Press the configuration pushbutton with a screwdriver for less than 0.5 sec => actuator enters teach-in mode, the 
    LED in the actuator is on 
4. Close contact of the binary input 
5. The LED in the actuator flashes twice for confirmation 
6. Press the configuration pushbutton with a screwdriver for less than 0.5 sec => actuator leaves teach-in mode 

Summary of Contents for xComfort F94 Series

Page 1: ...ule CP902xx Clip on plate Typical Application Scope of delivery Mounting Frame Decorative Plastic Metal Plate Style List No List Finish List No Finish Surface Mounting Frame F9400 CP902WH White CP902SS Stainless Steel CP902BM Black Matt CP902HP Highly Polished Copa Flush 2 Module C902 CP902GL Gold Metalic CP902SB Satin Bronze CP902SL Silver Metalic CP902PB Polished Brass CP902BL Blue Metalic CP902...

Page 2: ... 5 1a 3 6 7 1b 4 Click P9400 Surface Mounted on flat surface P9400 Flush Mounted on wall box P9400 Surface Flush mount with clip on cover Screw caps if required 4 x Click Flush mount Premera Frame e g P902 ...

Page 3: ... screwdriver to release module from surface plate Mounting screws Screw caps if fitted Remover screw cap discs if fitted along with mounting screws to release flush plate from wall box and allow access to battery at rear of module Note If Push button modules are either mounted on metal back boxes or used with metal clip on plates then the RF range may be restricted ...

Page 4: ...lashes twice for confirmation 4 Press the configuration pushbutton with a screwdriver for less than 0 5 sec actuator leaves teach in mode Assign a room thermostat to an actuator 1 Press the configuration pushbutton with a screwdriver for less than 0 5 sec actuator enters teach in mode the LED in the actuator is on 2 Turn the control knob to 3 The LED in the actuator flashes twice for confirmation ...

Page 5: ...2 Press the selected remote push button until the LED has flashed 5 times 3 Press the configuration pushbutton with a screwdriver for less than 0 5 sec actuator leaves teach in mode Unlink an assigned room thermostat 1 Press the configuration pushbutton with a screwdriver for less than 0 5 sec actuator enters teach in mode the LED in the actuator is on 2 Turn the control knob on the room thermosta...

Page 6: ...onfiguration pushbutton with a Screwdriver for longer than 2 sec actuator enters the manual mode for 10 sec the LED flashes fast 2 Press the configuration pushbutton with a screwdriver for less than 0 5 sec Shutter moves up 3 Press the configuration pushbutton with a screwdriver for less than 0 5 sec Shutter moves down 4 After 10 sec the actuator leaves automatically the manual mode 4 Reset actuat...

Page 7: ...w sent to the router and from there forwarded to the actuator The LED in the actuator flashes twice for confirmation 5 Finally press the configuration pushbutton with a screwdriver for less than 0 5 sec actuator leaves teach in mode 6 Configure two routers CROU 00 01 in Basic Mode 1 If the range of a single router is not sufficient a second one can be added to extend RF range further 2 Assign a pu...

Page 8: ...s to all listed types within our actual product catalog provided that it is installed maintained and used in the application intended for with respect to the relevant manufacturers instructions installation standards and good engineering practices complies with the provisions of Council directive s EMC Directive 2004 108 EC Radio and Telecommunications Terminal Equipment 99 05 EC based on complian...