12
Instruction Booklet
IB131024EN
Effective November 2017
38 kV Type VCPW-HD Simple Electrical
Ground & Test Device (SEG&TD) lower
terminal instruction booklet
EATON
www.eaton.com
Figure 40. Remote operator plugged into its receptacle and the
selector switch in the “Close” position.
14. On the remote operator, depress “Close” button momentarily.
The 38 kV SEG&TD will charge and close automatically (see
Figure 41). Note that the device has self-sealing capability and
does not require a "Close" button to be depressed until 38 kV
SEG&TD is closed. (The incoming feeder is grounded.)
Figure 41. Depressing the "Close" button momentarily on the
remote operator.
15. Insert key “KU” into Lock #1 and rotate to release key “KB”.
This electrically disables the 38 kV SEG&TD (see Figure 42).
16. Insert key “KB” into Lock #4 and rotate key “KD” to release
and store in Utility Box. This mechanically locks the
38 kV SEG&TD in the “Close” condition. (38kV SEG&T device
cannot be opened (see Figure 42).
Noticee:
At this point the 38kV SEG&TD has “Grounded the
Incoming Feeder”.
Key
outside
SEOG&TD
Key captured in - at end of 3.3 Step 16
Selector
switch
KK # 1
KK # 2
KK # 3
KK # 4
KK # 5
KD
KU
KC
No key
KB
No key
CLOSE
Figure 42. Key “KU” in Lock #1 and key “KB” in Lock #1.
3.4 Un-grounding the incoming feeder
Key
outside
SEOG&TD
Key captured in- at end of 3/3 Ste[ 16
Selector
switch
KK # 1
KK # 2
KK # 3
KK # 4
KK # 5
KD
KU
KC
No key
KB
No key
CLOSE
1. Selector Switch is in the “OFF” position. Keys should be in the
positions from Step 3.3.16.
2. Obtain key “KD” from the Utility lockbox.
3. Insert key “KD” into Lock #4. Release key “KB” and place into
Lock #1. This electrically enables the 38 kV SEG&TD.
4. Release key “KU” and place into Utility Box.
5. Make sure the selector switch is in the “Off”’ position (see
Figure 38).
otee:
N
The selector switch handle may appear slightly different (“T” or “L”
shape) however; both operate the same way.
Key
outside
SEOG&TD
Key captured in
Selector
switch
KK # 1
KK # 2
KK # 3
KK # 4
KK # 5
KU
KB
KC
No key
KD
No key
OFF
6. Insert the remote operator connector into the receptacle in the
front of the 38 kV SEG&TD (Figure 39).
7. Rotate the selector switch to the “Open”’ position (Figure 7).
8. On the remote operator, momentarily depress the “Open” but-
ton (Figure 54). The 38 kV SEG&TD will open.
Key
outside
SEOG&TD
Key captured in
Selector
switch
KK # 1
KK # 2
KK # 3
KK # 4
KK # 5
KU
KB
KC
No key
KD
No key
OPEN