6 Assembly/installation US-S ESF30 28-P und 13-P
6.3 Instructions for unhinging the doors
The doors are unhinged by pushing the pins from the leafs.
For safety reasons, the door panels should always be un-
hinged by at least 2 persons.
6.4 Fixing the hanging brackets onto the rear
of the enclosure
6.5 Choosing the wall plugs
For the fastening are generally building supervision or Euro-
pean technically approved or European technical rated dowels
with steel screws, which are suitable for the purpose of use,
according to the static requirements.
The special provisions of the respective general building
supervisory or European technical approval or European
assessment shall be observed.
The choice of suitable wall plugs for masonry must be made
depending on the type of blocks (solid or perforated masonry
blocks) and the different materials such as clay brick, lime-
sandstone or normal, lightweight or cellular.
The wall plugs supplied by us are suitable for DIN masonry
and blocks.
In case of unknown masonry, plug pull-out tests must be
performed!
6.6 EHL/ESL wall fixing
• The wall for mounting the enclosure on must be flat with
no unevenness!
• Align the fire enclosure horizontally on the wall.
• Mark on the predrilling marks through the hanging brackets
at the top.
• Make the holes for the enclosure fixing.
• Knock in the frame plugs.
• Attach the housing.
• If necessary, the doors must be re-hung.
• Seal the connection side wall to the side of the wall with
silicone.
• Ventilation openings above and below must kept free!