f
f
f
f
M
M
f
f
Locking with padlock when earthing disconnector
is ON, Break switch is OFF.
To put the padlock, rotate the padlock key to the
right, close the earthing switch operation hole put the
padlock.
Locking with padlock when earthing switch OFF LBS
OFF.
This lock is used in order to prevent the close the earth
switch if the switchgear as incoming switchgear and
cable.
SAFE OPERATION
Switchgear front cover can only be removed or attached when the earthing disconnector is ON.
I
I
Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual
May 2020 www.eaton.com
13