Tripp Lite by Eaton SmartPro Advanced User Guide 614-40195—Rev 01
43
3000 > 85%
Frequency regulation
+/-0.1 Hz
Nominal output
200/208/220/230/240V100/110/120/125Vt
Frequency
Follows input frequency
50/60Hz
Output overload
[105%,120%] 30min
[120%,150%] 5min
>150% 10s
[105% ~110%] 10s
[110% ~150%] 1s,
>150% 0.15s
Short circuit current limitation in
battery mode
Model
Current limitation
1500
38A
3000
64A
Transfer time
Utility Outage: 1-4ms for normal mode, >5ms for sensitive mode
Utility abnormal: <10ms for normal mode ,<25ms for sensitive mode
88..77
EElleeccttrriiccaall O
Ouuttppuutt C
Coonnnneeccttiioonn
Catalog Number
Output connection
Output cable
SMX1500XLRT2U
SMX1500XLRT2UN
(4) IEC10A Primary group
(2) IEC10A Group 1
(2) IEC10A Group 2
(2) IEC10A
SMX3000XLRT2UA
SMX3000XLRT2UN
(4) (1) IEC16A Primary group
(2) (1) IEC16A Group 1
(2) IEC10A Group 2
88..88
B
Baatttteerryy
Internal batteries
EBM
Specifications
1500VA: 48Vdc - 4 x 12V, 9Ah
3000VA: 72Vdc - 6 x 12V, 9Ah
BP48VRM2U: 48Vdc - 2 x 4 x 12V, 2 x
9Ah
BP72VRM2U: 72Vdc - 2 x 6 x 12V, 2 x
9Ah
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-5 year float
service life at 25°C (77°F).
Monitoring
Advanced monitoring for earlier failure detection and warning
EBM battery cable length
2U EBM cable length
:
350mm/13.78in
Summary of Contents for Tripp Lite SmartPro Series
Page 6: ......
Page 10: ...x Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 List of Figures...
Page 12: ...xii Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 List of Tables...
Page 16: ...4 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Introduction...
Page 28: ...16 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Installation...
Page 44: ...32 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Operation...
Page 58: ...614 4019501 614 40195 01...