Tripp Lite by Eaton SmartPro Advanced User Guide 614-40195—Rev 01
37
C
Chhaapptteerr 77 TTrroouubblleesshhoooottiinngg
The Eaton Tripp Lite Series SmartPro is designed for reliable, autonomous operation while providing you with
notifications and alerts whenever a potential operational or performance issue occurs. is designed for durable,
automatic operation and alerts you whenever potential operating problem may occur.
Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are
preventive alarms intended to alert the user.
•
Events are silent status information that are recorded into the Event log. Example = "AC NOT PRESENT".
•
Alarms are recorded into the Event log and displayed on the LCD status screen. Some alarms may be
announced by a beep every 3 seconds. Example = "BATTERY LOW".
•
Faults are announced by a continuous beep and red LED, recorded into the EVENT log and displayed on
the LCD with a specific message box or Fault code. Example = "OVER LOAD!" or "FAULT #007".
Use the following troubleshooting chart to determine the UPS alarm condition.
77..11
TTyyppiiccaall A
Allaarrm
mss aanndd FFaauullttss
To check the Event log or Fault log:
1. Press any button on the front panel display to activate the menu options.
2. Press the button to select Event log.
3. Scroll through the listed events or faults.
The following table describes typical conditions:
Table 25. Alarm Conditions
Conditions
Possible cause
Action
Battery mode
LED is On.
1 beep every 10 seconds
A utility failure has occurred and the UPS
is in battery mode.
The UPS is powering the equipment with battery
power. Prepare your equipment for shutdown.
Battery low
LED is On.
1 beep every 3 seconds
The UPS is in Battery mode and the
battery is running low.
This warning is approximate, and the actual time
to shutdown may vary significantly. Depending on
the UPS load and number of Extended Battery
Modules (EBMs), the "BATTERY LOW" warning
may occur before the remaining time reaches 3
minutes by default.
No battery
LED is On
Beep continuous
The batteries are disconnected.
Verify that all batteries are properly connected. If
the condition persists, contact your service
representative.
Battery fault
The battery test is failed due to bad or
disconnected batteries.
Verify that all batteries are properly connected. If
the condition persists, contact your service
representative.
Summary of Contents for Tripp Lite SmartPro Series
Page 6: ......
Page 10: ...x Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 List of Figures...
Page 12: ...xii Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 List of Tables...
Page 16: ...4 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Introduction...
Page 28: ...16 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Installation...
Page 44: ...32 Tripp Lite by Eaton SmartPro Advanced User Guide 614 40195 Rev 01 Operation...
Page 58: ...614 4019501 614 40195 01...