44
Output overload
100-105% : no alarm
105-125% : load transfers to Bypass mode after 10 minutes
125-150% : load transfers to Bypass mode after 30s
> 150%
: load transfers to Bypass mode after
Output overload
(Bypass mode)
100-105% : no alarm
105-125% : continue working and alarm
125-150% : UPS shuts down after 30s
Voltage waveform
Sinewave
Harmonic distortion
< 1% THDV on linear load
< 5% THDV on non-linear load
Transfer time
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Power factor
1
Load crest ratio
3 to 1
* for 208V output, the load level will be derating to 90%.
Table 7. Electrical output connections
Model
Output connection
Output cable
Tower 6K/6KS
Hardwired
Not provided
Tower 10K/10KS
Table 8. Environmental and safety
Certifications
EN 62040-1
IEC/EN 62040-2: Cat. C3
IEC/EN 62040-3
EN 60950-1
EMC (Emissions)*
Conduction: C3 IEC/EN 62040-2
Radiation: C3 IEC/EN 62040-2
EMC (Immunity)
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports) IEC 61000-4-5, Level
4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
* for output cable < 10m.
Agency markings
CE
Operating
temperature
0~40
℃
full load no derating
40~50
℃
output power derating to 50% load, Charger current
derating 50%