22
Power strategy [normal] [high efficiency] [converter]
[normal]
Auto bypass
[enabled] [disabled]
[enabled]
Auto restart
[enabled] [disabled]
Authorize the product to restart
automatically when mains recovers after a
complete battery discharge.
[enabled]
Dry in
[Disabled] [SON] [SOFF] [Maintain bypass] [Disabled]
Dry out
[Load powered] [On battery mode] [Battery
low] [Battery disconnected] [Bypass output]
[UPS normal]
[Load powered]
Start on battery [enabled] [disabled]
[enabled]
External battery
modules
[0~20]
According to model
External battery
AH setting
[0~300]
According to model
Battery
remaining time
[enabled] [disabled]
[enabled]
Charger current [0~4] 0~4A for standard model
[0~12] 0~12A for long backup model
[1.4A] for 6K
[2A] for 10K
[4A] for 6KS/10KS
Site wiring fault
alarm
[disabled] [enabled]
[disabled]
LCD contrast
[-5 ~ +5]
[+0]
5.5 UPS startup and shutdown
Please make sure there is no load connected to the ups before the ups is turned
on, and take on the load one by one after the UPS is turned on.
Take off all of the connected loads before turning off the UPS.
Starting the UPS with utility
Verify that the total equipment ratings do not exceed the UPS capacity to
prevent an overload alarm.
Start the UPS with utility:
Check all the connection is correct.
Power on the UPS, the fan begins to rotate. After that, the LCD will show the
default UPS status summary screen.
Pressing button continuously for more than 1 second, the buzzer will beep
300ms, UPS starts to turn on.