40
BUS Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F021
Indicates that the UPS get BUS
over voltage fault because of
BUS.
The UPS transfers to
Bypass mode if supporting
the load
BUS Under Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F022
Indicates that the UPS get BUS
under voltage fault
The UPS transfers to
Bypass mode if supporting
the load
BUS Unbalance
Fault (Red) LED is On.
Beep continuous.
Code: F023
Indicates that the positive BUS
voltage and negative BUS
voltage are too lopsided to
fault
The UPS transfers to
Bypass mode if supporting
the load
BUS Short
Fault (Red) LED is On.
Beep continuous.
Code: F024
Indicates that the BUS voltage
decrease very fast
Contact your service
representative
BUS Softstart Fail
Fault (Red) LED is On.
Beep continuous.
Code: F025
Indicates that the BUS could
not soft start successfully
Contact your service
representative
Inv Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F032
Indicates that the UPS get
invert over voltage fault
The UPS transfers to
Bypass mode if supporting
the load
Inv Under Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F033
Indicates that the UPS get
inverter under voltage fault
The UPS transfers to
Bypass mode if supporting
the load
Inv Softstart Fail
Fault (Red) LED is On.
Beep continuous.
Code: F034
Indicates that the inverter
could not soft start successfully
Contact your service
representative
Charger Fail
Fault (Red) LED is
flash
1 beep every 1 second
Code: A015
Indicates that the UPS has
confirmed the charger has
failed
The UPS turns off the
charger until the next
power recycle. Contact
your service representative