Instruction Leaflet 

IL 29C703D

Effective April 2011

Installation Instructions for Eaton Series C 600 Amp HLD-DC 

Circuit Breakers, Circuit Breaker Frame and Molded Case Switch 

EATON CORPORATION www.eaton.com

4. Inspection and Field Testing 

Series C molded case circuit breakers are designed to provide years 

of almost maintenance-free operation . The following procedure 

describes how to do a limited amount of field inspection and testing 

of a circuit breaker . 

Inspection 

Circuit breakers in service should be inspected periodically . The 

inspection should include the following checks: 4-1 through 4-7 .

D

D

WARNING

THEDVOLTAGESDINDENERGIZEDDEQUIPMENTDCANDCAUSEDSEVERED

PERSONALDINJURYDORDDEATH.DBEFOREDINSPECTINGDTHEDCIRCUITD

BREAKERDINDANDELECTRICALDSYSTEM,DMAKEDSUREDTHEDCIRCUITDBREAKERD

ISDSWITCHEDDTODTHEDOFFDPOSITIONDANDDTHATDTHEREDISDNODVOLTAGED

PRESENTDWHEREDWORKDISDTODBEDPERFORMED.D

D

D

CAUTION

SOMEDCOMMERCIALDCLEANINGDAGENTSDWILLDDAMAGEDTHED

NAMEPLATESDORDMOLDEDDPARTS.DMAKEDSUREDTHATDCLEANINGDAGENTSD

ORDSOLVENTSDUSEDDTODCLEANDTHEDCIRCUITDBREAKERDAREDSUITABLEDFORD

THEDJOB.

4-1 .  Remove dust, dirt, soot, grease or moisture from the surface 

of the circuit breaker using a lint-free dry cloth, brush or vacu-

um cleaner . Do not blow debris into circuit breaker . If contami-

nation is found, look for the source and eliminate the problem . 

4-2 .  Switch the circuit breaker to ON and OFF several times to be 

sure that the mechanical linkages operate freely and do not 

bind . If mechanical linkages do not operate freely, replace cir-

cuit breaker .

4-3 .  With the circuit breaker in the ON position, press the PUSH-

TO-TRIP button to mechanically trip the circuit beaker . Trip, 

reset and switch the circuit breaker ON several times . If the 

mechanism does not reset each time the circuit breaker is 

tripped, replace the circuit breaker . 

4-4 .  Check base, cover, operating handle and the handle barrier for 

cracks, chipping and discoloration . Circuit breakers should be 

replaced if cracks or severe discoloration is found . 

4-5 .  Check wire connecting terminals and other type bus bar con-

nectors for looseness or signs of overheating . Overheating 

will show as discoloration, melting or blistering of conductor 

insulation, or as pitting or melting of conductor surfaces due 

to arcing . If there is no evidence of overheating or looseness 

do not disturb or tighten the connections . If there is evidence 

of overheating, terminations should be cleaned or replaced . 

Before re-energizing the circuit breaker, all terminations and 

cable should be refurbished to the original installed condition . 

4-6 .  Check circuit breaker mounting hardware and tighten if neces-

sary . 

4-7 .  Exposure to certain types of chemicals can lead to deteriora-

tion of electrical connections . Check area where circuit break-

er is installed for any safety hazards, including personal safety 

and fire hazards and take required precautionary actions . 

Field Testing 

Any field-testing should be done in accordance with applicable 

NEMA Standard .

Summary of Contents for TA602LD

Page 1: ...ation and Thermal Magnetic Trip Unit Adjustment 5 Inspection and Field Testing 6 Effective April 2011 Supersedes IL 29C703C Dated 07 1998 Instruction Leaflet IL 29C703D Installation Instructions for E...

Page 2: ...gment but should not be considered to be all inclusive or covering every application or circumstance which may arise Contact Eaton for further information or instructions 1 Introduction and General In...

Page 3: ...2 1 Compare nameplate data with existing equipment ratings and system requirements to make sure that the circuit breaker is suitable for the intended installation Prior to mounting confirm that the c...

Page 4: ...on the mounting surface d Install circuit breaker mounting screws and washers Tighten screws firmly but do not exceed 28 lb in 3 N m Figure 7 3 Pole Circuit Breaker Mounting Bolt Drilling Plans Figur...

Page 5: ...ustment Manual Operation The circuit breaker handle and the Push To Trip button in the trip unit control manual operation of the circuit breaker The circuit breaker handle has three positions two of w...

Page 6: ...times to be sure that the mechanical linkages operate freely and do not bind If mechanical linkages do not operate freely replace cir cuit breaker 4 3 With the circuit breaker in the ON position pres...

Page 7: ...uction Leaflet IL 29C703D Effective April 2011 Installation Instructions for Eaton Series C 600 Amp HLD DC Circuit Breakers Circuit Breaker Frame and Molded Case Switch EATON CORPORATION www eaton com...

Page 8: ...sidered all inclusive If further information is required you should consult an authorized Eaton sales representative The sale of the product shown in this literature is subject to the terms and condit...

Reviews: