Operation
16
Eaton T2235 Series eATS ePDUs P-164000014—Rev 1
www.eaton.com/ePDU
Circuit Breakers
Circuit breakers protect the power controller and all devices connected to it from fault conditions, such as a
short circuit or an overload. Circuit breakers are optional for ePDUs with less than 30A input. However, circuit
breakers are mandatory for ePDUs with 30A input or greater.
!
IMPORTANT
If a supplementary protector is used in the ePDU instead of a listed circuit breaker, additional
branch circuit protection is required down-line from the power source to the ePDU.
Power Outlets
All outlets are on the rear panel. Power is available to the switched outlets after the main power is either
connected or the optional breaker is set to the ON position.
Auto-Transfer Primary to Secondary
Firm drop-out voltage points allow a transfer before an undervoltage affects equipment operation.
Table 2 shows the transfer voltage ranges.
Sources do not need to be phase synchronized. Source transfer time is less than 30 ms. (The front panel LEDs
indicate which sources are available and selected at the output, as shown in Figure 5.)
Optional EMI/RFI Filtering
EMI/RFI Filtering (Option 3)
Power filtering reduces the effects of EMI or RFI. This type of “noise” can be introduced from many sources,
inside or outside your facility. The filtering is bi-directional, so it helps prevent emissions from connected
equipment. Select “F” in Option 3 to include EMI/RFI Filtering or “N” to exclude it.
Table 3 shows EMI Filter Specifications.
Table 2. Transfer Voltage Ranges
Nominal Voltage
Drop-Out Voltage
Pull-In Voltage
120V
90V
103V
208V
182V
195V
240V
197V
210V
Table 3. EMI Filter Specifications
Common mode insertion loss
Differential mode insertion loss
Specification
Line-to-Ground in 50 ohm circuit
Line-to-Line in 50 ohm circuit
Current rating
20A
20A
MHz
dB
dB
240 V
197V
210V
* The rated voltage is 120/250 Vac. The operating frequency is 50/60 Hz.
Summary of Contents for T2235 Series
Page 5: ...Table of Contents ii Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Page 9: ...Introduction 4 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Page 13: ...Safety 8 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Page 19: ...Installation 14 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Page 23: ...Operation 18 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Page 25: ...Maintenance 20 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Page 35: ...Service 30 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Page 39: ...Warranty 34 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...