Lights will not remain ON
occupancy sensitivity may be set to LO
• Verify that the sensor’s red LED flashes with motion activity.
• Using the programming remote (ISHH-01) ensure the relay can be turned
ON/OFF.
• Using the programming remote (ISHH-01) push the “HI” button to ensure
occupancy coverage area is maximized.
daylight switching may be enabled in error
• Using the programming remote (ISHH-01) ensure the relay can be turned
ON/OFF.
• Follow the steps in this document ensure that daylight switching is
disabled.
Lights will not turn OFF
automatically
occupancy placement or sensitivity
• Using the programming remote (ISHH-01) ensure the relay can be turned
ON/OFF.
• Verify that the sensor’s red LED flashes with motion activity and stops
flashing with no motion.
• If the LED flashes when motion is not occurring, ensure the sensor is not
located within 4-6 feet of air vents.
• If the LED is flashing when motion is not occurring, using the
programming remote (ISHH-01) push the “LO” button to reduce
occupancy coverage area.
unoccupied scene set to ON in error
• Using the programming remote (ISHH-01) ensure the relay can be turned
ON/OFF.
• If the load turns ON with the remote, follow the steps in this document to
set the unoccupied scene level.
Lights turn ON but remain
at a dimmed level
0-10V output
• Using the programming remote (ISHH-01) ensure the relay can be turned
ON/OFF and the light level can be raised and lowered.
• If still not responsive, disconnect the 0-10V wires from the control
module. If the lighting does not go to full bright check wiring for shorts.
• Verify with a meter that at least 10VDC is present between the purple
and gray disconnected driver leads.
• If the lighting does go full bright when disconnected from the control
module, check for polarity reversal on the 0-10V leads.
daylight dimming is enabled where not
appropriate
AND/OR
occupancy detection scene level set too low
• Using the programming remote (ISHH-01) ensure the relay can be turned
ON/OFF and the light level can be raised and lowered.
• If the load turns ON and responds to the raise/lower commands,
determine whether the fixture should dim with daylighting. If it should
not, follow the steps in this document to disable daylight dimming and
then set the occupancy detection scene level.
• If the load should dim with daylighting, it may need recalibration. Follow
the steps in this document to set the occupancy detection scene level.
Lights turn ON but remain
at full bright level
0-10V output
• Using the programming remote (ISHH-01) ensure the relay can be turned
ON/OFF and the light level can be raised and lowered.
• If still not responsive, disconnect the 0-10V wires from the control
module. Lighting should remain full bright.
• Temporarily connect the driver’s purple and gray wires together. Verify
the lighting goes full dim.
• Verify with a meter that at least 10VDC is present between the purple
and gray disconnected driver leads.
• If the lighting goes full bright again when the leads are separated after
this test, check for polarity reversal on the 0-10V leads.
daylight dimming is disabled in error
AND/OR
occupancy detection scene level set too high
• Using the programming remote (ISHH-01) ensure the relay can be turned
ON/OFF and the light level can be raised and lowered.
• If the load turns ON and responds to the raise/lower commands, follow
the steps in this document to ensure that daylight dimming is enabled
and then set the occupancy detection scene level.