3
SVPD Programming Guide
www.eaton.com/lightingsystems
Features and Default Settings
This programming guide discusses how to modify the basic out-of-the-box behavior of the SVPD series sensor (SVPD1, SVPD2, SVPD3). The
SVPD series integrated sensor allows for quick and easy control of individual luminaires. Out-of-the box, the SVPD integrated sensor will:
• Turn ON lighting to 100% based on occupancy (daylight adjustment may reduce light level).
• Reduce lighting during daylight hours based on the availability of natural daylight.
• Turn off lighting automatically when no occupancy is detected for a period of 20 minutes.
Feature
Description
Default
User Programmable Settings
Occupancy detection
scene level
The light level the fixture will go to when
occupancy is detected. If daylight dimming is
enabled, when the fixture is in this scene at night
the integrated sensor will “capture” the light
level. The fixture will use this “captured” level
as a target to dim the electric lighting during the
daytime hours.
Auto-ON to 100%
1
• Yes. Adjust to any desired light
level.
• Adjust to modify daylight dimming
or daylight switching target light
level
2
.
Occupancy energy saver
scene level
The light level that the fixture will reduce to if
the space remains unoccupied for half of the
occupancy time-out period.
100% - Occupancy Detection Scene
Yes. Adjust to any desired light level.
Unoccupied scene level
The light level that the fixture will go to when the
space remains unoccupied for the full amount of
the programmed occupancy time-out period.
OFF
Yes. Adjust to any desired light level.
Occupancy time-out
The period of time that the lighting will remain
at the current level after the space becomes
unoccupied.
20 min.
Yes. Adjust to 5, 10, 15, or 20
minutes.
Occupancy sensitivity
Adjusts the motion activity coverage area.
Sensors that pick up motion activity beyond the
desired area may be set to “LO” to reduce false
triggering.
High
Yes. Adjust to high or low.
Daylight dimming
Automatically dims the electric lighting in
response to natural daylight in the space.
Enabled
Yes. Disable or enable daylight
dimming.
Daylight switching
3
Automatically turns OFF the fixture through an
internal relay when daylight contribution exceeds
150% of the maximum nighttime light level
output (based on occupancy detection scene light
level captured at night). Lighting will remain OFF
for 30 minutes and then re-evaluate based on the
light level and occupied state.
Disabled
Yes. Disable or enable daylight
switching.
1
If daylight dimming is enabled, the fixture may dim below this level based on available daylight.
2
If daylight dimming or daylight switching are enabled, adjustments to the occupancy detection scene will raise or lower the target level for
the daylight dimming or daylight switching.
3
Daylight switching is recommended only for outdoor applications.