Effective January 2019
4
Eaton SPD Series for Mounting External
to Electrical Distribution Equipment
Instruction Manual
IM01005031E - Rev. 6
7. Determine the wire length for the Ground and Neutral (where
applicable) wires and cut these wires as needed. Again, keep
these wires as short as possible to maximize SPD perfor-
mance.
8. Standard and Standard with Surge Counter SPDs also provide
wiring for Form C relay contacts. This connection can be used
for remote monitoring of the SPD. The Form C contacts are
rated at 150V AC or 125V DC at 1A. Make the remote moni-
toring connections per the Form C wiring diagram in Figure 8
Follow all national, state and local electrical codes when mak-
ing these connections.
Figure 2. NEMA 1 (With Flushmount) (Suffix L)
4
IM01005031E
Rev. 2
Effective November
20
12
Eaton SPD Series
For Mounting External To
Electrical Distribution Equipment
eaton corporation
www.eaton.com
Determine the wire length for the Ground and Neutral
7.
(where applicable) wires and cut these wires as needed.
Again, keep these wires as short as possible to maximize
SPD performance.
Standard and Standard with Surge Counter SPDs also pro-
8.
vide wiring for Form C relay contacts. This connection can be
used for remote monitoring of the SPD. The Form C contacts are
rated at 150V AC or 125V DC at 1A. Make the remote monitoring
connections per the Form C wiring diagram in Figure 7. Follow
all national, state and local electrical codes when making
these connections.
NEMA 1 (With Flushmount) (Suffix L)
Figure 2.