background image

Instruction Manual 

IM01005031E - Rev.6

Effective January 2019

Eaton 

www.eaton.com

        13 

Eaton SPD Series for Mounting External

to Electrical Distribution Equipment

Examplee: SPD 250480D2K = SPD Series, 250kA Per Phase, 480D Voltage, Standard Feature Package, NEMA 1 Sidemount Application.    

 

 

 

 

 

      SPD   250   480D   2   J

SPD

kA Rating

Options

50kA Per Phase
80kA Per Phase
100kA Per Phase
120kA Per Phase 
160kA Per Phase
200kA Per Phase
250kA Per Phase
300kA Per Phase
400kA Per Phase

Feature Package

Options

1

 = Basic. 

 

    Dual colored LED per Phase to indicate Protection status 

 

    Dual colored LED to indicate protection status of the N-G Mode on

                           units with a Neutral Wire

2

 = Standard. 

 

    Dual colored LED Per Phase to indicate Protection Status

 

    Dual colored LED to indicate Protection Status of the N-G Mode on 

                           units with a Neutral Wire 
 

    Audible alarm with Silence button 

 

    Form 'C' Relay Contact. See Table 4 Specifications  

                      EMI/RFI filtering Providing up to 50dB of Noise Attenuation from
                          10KHz to 100Mhz

3

 = Standard With Surge Counter 

 

   

Dual colored LED Per Phase to indicate Protection Status 

                      Dual colored LED to indicate Protection Status of the N-G Mode on  
                           units with a Neutral Wire
                      Audible alarm with Silence button     

     

     

    

                      Form 'C' Relay Contact    
                      EMI/RFI filtering Providing up to 50dB of Noise Attenuation from   

 

    

10kHz to 100Mhz  

         

                      

Surge Counter with Reset Button

Application Suffix

Options

Sidemount Units

K

 = NEMA 1 Enclosure 

L

 = NEMA 1 Flushmount Enclosure (Available in 50-200kA Ratings Only) 

M

 = NEMA 1 Enclosure With Internal Disconnect

N

 = NEMA 4 Enclosure

O

 = NEMA 4 Enclosure With Internal Disconnect

P

 = NEMA 4X Enclosure 

Q

 = NEMA 4X Enclosure With Internal Disconnect 

For units 50-200 kA in a NEMA 1 rated enclosure: SPDGREYFLUSHMTKIT

Voltage Code 

Options

Sidemount Units

240S

 = 120/240 Split Phase

208Y

 = 120/208 Wye (4W + G)

220Y

 = 127/220 Wye (4W + G)

400Y

 = 230/400 Wye (4W + G)

480Y

 = 277/480 Wye (4W + G)

600Y

 = 347/600 Wye (4W + G)

240D

 = 240 Delta (3W + G)

480D

 = 480 Delta (3W + G)

600D

 = 600 Delta (3W + G)

240H

 = 240 Delta High Leg (4W + G) on 'B' Phase

230L

 

=  230 Single Phase*

NOTEe:

 Please consult the factory for 240 Delta HIgh 

Leg  (4W+G) applications with high leg on 'C' Phase   

6.0 Ordering Guidelines

Table 4.  Eaton SPD Series

**

Eaton’s Delta Catalog numbers

 SPD120480D3M, SPD160480D3M 

and 

SPD200480D3M 

meet the requirements of IEC 61643-11 / EN 61643-11, Part 11: 

Test Class II, and are intended to be installed in applications with a degree of protection rated IP 20.

Summary of Contents for SPD Series

Page 1: ...l Distribution Equipment Instruction Manual IM01005031E Effective November 2012 Rev 2 Table of Contents 1 0 Introduction 2 0 Installation 3 0 Operating Features 4 0 Troubleshooting 5 0 Specifications 6 0 Ordering Guidelines 7 0 Warranty Eaton SPD Series For Mounting External To Electrical Distribution Equipment ...

Page 2: ...and are intended to be installed in applications with a degree of protection rated IP 20 1 3 Safety Precautions A licensed qualified electrician must complete all instructions in this manual in accordance with the National Electric Code NEC state and local codes or other applicable country codes All applicable local electrical codes supersede these instructions WARNING IMPROPER INSTALLATION COULD ...

Page 3: ...heck the facility grounding system All grounding bonding and earthing must meet the NEC and any other national state and local electrical codes 2 2 Installation Locations Eaton s SPD Series can be installed next to above or below any existing electrical enclosure The ideal mounting location for the Eaton SPD Series is as close as possible to the electrical enclosure The Eaton SPD Series should be ...

Page 4: ...state and local electrical codes when mak ing these connections Figure 2 NEMA 1 With Flushmount Suffix L 4 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com Determine the wire length for the Ground and Neutral 7 where applicable wires and cut these wires as needed Again keep these wires as short as ...

Page 5: ...x K Figure 4 NEMA 4 4X Suffix N P 5 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting ExternalTo Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 Suffix K Figure 3 NEMA 4 4X Suffix N P Figure 4 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting ExternalTo Electrical Distribution Equipment NEMA 1 Suffix K Figure 3 ...

Page 6: ...ev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 With Disconnect Suffix M Figure 5 NEMA 4 4X With Disconnect Suffix O Q Figure 6 6 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 With Disconnect S...

Page 7: ...ual IM01005031E Rev 6 Effective January 2019 Eaton www eaton com 7 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Figure 7 Flush Mount Plate For 50 200 kA Units In A NEMA 1 Rated Enclosure ...

Page 8: ...ion Equipment Instruction Manual IM01005031E Rev 6 BLUE WHITE RED WHITE ORANGE WHITE COMMON NORMALLY OPEN NORMALLY CLOSED Figure 8 Sidemount Form C Wires Figure 9 Split Phase Units Figure 10 3 Phase Delta Figure 11 3 Phase Wye Units Figure 12 High Leg Delta Units Contact Factory if High Leg is not on Phase B ...

Page 9: ...nt for each feature package Each display has both green and red light emitting diodes LEDs to indicate the status of the protection on each phase Green indicates the phase is fully protected Red indicates a loss of protection Wye Split Phase and High Leg Delta units have an additional set of green red LEDs to indicate status of Neutral Ground protection When the LEDs turn red an audible alarm will...

Page 10: ... the display 3 Remove the two phillips head screws that hold the display 4 Rotate the display to the desired position Be careful not to overstress the display ribbon cable 5 Place the display back onto the SPD enclosure Again be careful not to overstress or crimp the ribbon cable 6 Replace the two phillips head screws Tighten screws to 1 35 Nm 12 in lbs 7 Restore power to the unit 3 3 IEC Approved...

Page 11: ...V Significant surge event Replace SPD Replace SPD with correct voltage model Check electrical system for TOV sources correct replace SPD Replace SPD One of the display Red LEDs is ON Audible Alarm is OFF Audible Alarm Silence button has been depressed and Alarm is silenced Normal operation If power is cycled and a fault condition still exists the Audible Alarm will reactivate All Green and Red LED...

Page 12: ...and 480D Basic voltage codes 600Y and 600D voltage codes 0 6W 1 7W 2 1W Protection modes Single split phase L N L G N G L L Single phase L N L G N G Three phase delta L G L L Three phase Wye L N L G N G L L Three phase high leg delta L N L G N G L L Maximum continuous operating voltage MCOV 208Y 220Y 240S 240D and 240H voltage codes 150 L N 150 L G 150 N G 300 L L 230L 400Y and 480Y voltage codes ...

Page 13: ...ate Protection Status of the N G Mode on units with a Neutral Wire Audible alarm with Silence button Form C Relay Contact EMI RFI filtering Providing up to 50dB of Noise Attenuation from 10kHz to 100Mhz Surge Counter with Reset Button Application Suffix Options Sidemount Units K NEMA 1 Enclosure L NEMA 1 Flushmount Enclosure Available in 50 200kA Ratings Only M NEMA 1 Enclosure With Internal Disco...

Page 14: ...ithin said term determined by Eaton to be defec tive The giving of or failure to give any advice or recommenda tions by Eaton shall not constitute any warranty by or impose any liability upon Eaton The foregoing constitutes the sole and exclusive liability of Eaton AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY FITNESS FOR PURPOSE SOLD DESCR...

Page 15: ...Instruction Manual IM01005031E Rev 6 Effective January 2019 Eaton www eaton com 15 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Notes ...

Page 16: ...and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATIO...

Reviews: