Instruction Manual
IM01005031E - Rev.6
Effective January 2019
13
Eaton SPD Series for Mounting External
to Electrical Distribution Equipment
Examplee: SPD 250480D2K = SPD Series, 250kA Per Phase, 480D Voltage, Standard Feature Package, NEMA 1 Sidemount Application.
SPD 250 480D 2 J
SPD
kA Rating
Options
50kA Per Phase
80kA Per Phase
100kA Per Phase
120kA Per Phase
160kA Per Phase
200kA Per Phase
250kA Per Phase
300kA Per Phase
400kA Per Phase
Feature Package
Options
1
= Basic.
Dual colored LED per Phase to indicate Protection status
Dual colored LED to indicate protection status of the N-G Mode on
units with a Neutral Wire
2
= Standard.
Dual colored LED Per Phase to indicate Protection Status
Dual colored LED to indicate Protection Status of the N-G Mode on
units with a Neutral Wire
Audible alarm with Silence button
Form 'C' Relay Contact. See Table 4 Specifications
EMI/RFI filtering Providing up to 50dB of Noise Attenuation from
10KHz to 100Mhz
3
= Standard With Surge Counter
Dual colored LED Per Phase to indicate Protection Status
Dual colored LED to indicate Protection Status of the N-G Mode on
units with a Neutral Wire
Audible alarm with Silence button
Form 'C' Relay Contact
EMI/RFI filtering Providing up to 50dB of Noise Attenuation from
10kHz to 100Mhz
Surge Counter with Reset Button
Application Suffix
Options
Sidemount Units
K
= NEMA 1 Enclosure
L
= NEMA 1 Flushmount Enclosure (Available in 50-200kA Ratings Only)
M
= NEMA 1 Enclosure With Internal Disconnect
N
= NEMA 4 Enclosure
O
= NEMA 4 Enclosure With Internal Disconnect
P
= NEMA 4X Enclosure
Q
= NEMA 4X Enclosure With Internal Disconnect
For units 50-200 kA in a NEMA 1 rated enclosure: SPDGREYFLUSHMTKIT
Voltage Code
Options
Sidemount Units
240S
= 120/240 Split Phase
208Y
= 120/208 Wye (4W + G)
220Y
= 127/220 Wye (4W + G)
400Y
= 230/400 Wye (4W + G)
480Y
= 277/480 Wye (4W + G)
600Y
= 347/600 Wye (4W + G)
240D
= 240 Delta (3W + G)
480D
= 480 Delta (3W + G)
600D
= 600 Delta (3W + G)
240H
= 240 Delta High Leg (4W + G) on 'B' Phase
230L
= 230 Single Phase*
NOTEe:
Please consult the factory for 240 Delta HIgh
Leg (4W+G) applications with high leg on 'C' Phase
6.0 Ordering Guidelines
Table 4. Eaton SPD Series
**
Eaton’s Delta Catalog numbers
SPD120480D3M, SPD160480D3M
and
SPD200480D3M
meet the requirements of IEC 61643-11 / EN 61643-11, Part 11:
Test Class II, and are intended to be installed in applications with a degree of protection rated IP 20.