Eaton SPD Series for Mounting External

to Electrical Distribution Equipment

Instruction Manual 

IM01005031E - Rev. 6

Description

Specification

Surge current capacity per phase

50, 80, 100, 120, 160, 200, 250, 300, 400 kA ratings available

Nominal discharge current (I

n

)

20kA

Short circuit current rating (SCCR)

200kA

SPD Type

Basic feature package = Type 1 (can also be used in Type 2 applications)

Standard and Standard with Surge Counter feature packages = Type 2

Enclosure Types

NEMA 1, NEMA 4, NEMA 4X (304 SST)

Standard split phase voltages available

120/240 

Single phase

230

Three phase wye system voltages available

120/208, 127/220, 230/400, 277/480, 347/600

Three phase delta system voltages

240, 480, 600

Three phase high leg delta system voltages

120/240

Phase wire length                                                                                  

48” of 10AWG extend beyond the conduit hub

Relay wire length (optional) 

48” of 14AWG extend beyond the conduit hub

RoHS Compliant                                                   

Yes

Internal Disconnect (optional)                             

Eaton 30 Amp FDC Circuit Breaker, Type MCCB

Input Power Frequency

50/60 Hz 

Power consumption (Basic units)

     208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes

     400Y and 480Y and 480D voltage codes

     600Y and 600D voltage codes

0.5W

1.1W

1.3W

Power consumption (Standard and Standard with Surge Counter units)

     208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes

     400Y, 480Y, and 480D Basic voltage codes

     600Y and 600D voltage codes

0.6W

1.7W

2.1W

Protection modes

Single split phase ...L-N, L-G, N-G, L-L   Single phase... L-N, L-G, N-G    Three phase delta...L-G, L-L 

Three phase Wye.....L-N, L-G, N-G, L-L   Three phase high leg delta....L-N, L-G, N-G, L-L

Maximum continuous operating voltage (MCOV)     

     208Y, 220Y, 240S, 240D, and 240H voltage codes

 

150 L-N,150 L-G, 150 N-G, 300 L-L

     230L, 400Y and 480Y voltage codes

320 L-N, 320 L-G, 320 N-G, 640 L-L

     600Y voltage code

420 L-N, 420 L-G, 420 N-G, 840 L-L

     240 D voltage code

320 L-G, 320 L-L

     480 D voltage code         

640L- L-G, 640 L-L

     600D voltage code

840 L-G, 840 L-L

Ports

1

Operating temperature

-40F to 122F (-40C to 50C)

Operating humidity

5% through 95%, non-condensing

Weight

Reference Figures 2, 3, 4, 5, and 6 on pages 4, 5 and 6

Form C relay contact ratings

150 Vac or 125 Vdc, 1A maximum

Form C relay contact loogic

Power  on, normal state - NO contact = OPEN, NC contact  = CLOSED

Power off, fault state, - NO contact = CLOSED, NC contact = OPEN 

EMI/RFI filtering attenuation (Standard and Standard With Surge Counter 

Up to 50 dB from 10 kHz to 100 MHz

Agency certifications and approvals 

UL1449 4th Edition listed, CSA (excludes 230L voltage code), UL1283 7th Edition (Type 2 SPDs only)

IEC 61643-11/EN 61643-11, Part 11: Test Class II.  See Section 6.0 Ordering Guidelines for specific models.

Warranty

10 Years, 15 Years if you register on www.eaton.com/spd and click the warranty registration icon.

ROHS Compliant

Yes

Wire Length and AWG

Factory prewired with 48 inches of 10 AWG wire.

5.0 Specifications

Table 3.  Specifications

Summary of Contents for SPD Series

Page 1: ...l Distribution Equipment Instruction Manual IM01005031E Effective November 2012 Rev 2 Table of Contents 1 0 Introduction 2 0 Installation 3 0 Operating Features 4 0 Troubleshooting 5 0 Specifications 6 0 Ordering Guidelines 7 0 Warranty Eaton SPD Series For Mounting External To Electrical Distribution Equipment ...

Page 2: ...and are intended to be installed in applications with a degree of protection rated IP 20 1 3 Safety Precautions A licensed qualified electrician must complete all instructions in this manual in accordance with the National Electric Code NEC state and local codes or other applicable country codes All applicable local electrical codes supersede these instructions WARNING IMPROPER INSTALLATION COULD ...

Page 3: ...heck the facility grounding system All grounding bonding and earthing must meet the NEC and any other national state and local electrical codes 2 2 Installation Locations Eaton s SPD Series can be installed next to above or below any existing electrical enclosure The ideal mounting location for the Eaton SPD Series is as close as possible to the electrical enclosure The Eaton SPD Series should be ...

Page 4: ...state and local electrical codes when mak ing these connections Figure 2 NEMA 1 With Flushmount Suffix L 4 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com Determine the wire length for the Ground and Neutral 7 where applicable wires and cut these wires as needed Again keep these wires as short as ...

Page 5: ...x K Figure 4 NEMA 4 4X Suffix N P 5 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting ExternalTo Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 Suffix K Figure 3 NEMA 4 4X Suffix N P Figure 4 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting ExternalTo Electrical Distribution Equipment NEMA 1 Suffix K Figure 3 ...

Page 6: ...ev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 With Disconnect Suffix M Figure 5 NEMA 4 4X With Disconnect Suffix O Q Figure 6 6 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 With Disconnect S...

Page 7: ...ual IM01005031E Rev 6 Effective January 2019 Eaton www eaton com 7 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Figure 7 Flush Mount Plate For 50 200 kA Units In A NEMA 1 Rated Enclosure ...

Page 8: ...ion Equipment Instruction Manual IM01005031E Rev 6 BLUE WHITE RED WHITE ORANGE WHITE COMMON NORMALLY OPEN NORMALLY CLOSED Figure 8 Sidemount Form C Wires Figure 9 Split Phase Units Figure 10 3 Phase Delta Figure 11 3 Phase Wye Units Figure 12 High Leg Delta Units Contact Factory if High Leg is not on Phase B ...

Page 9: ...nt for each feature package Each display has both green and red light emitting diodes LEDs to indicate the status of the protection on each phase Green indicates the phase is fully protected Red indicates a loss of protection Wye Split Phase and High Leg Delta units have an additional set of green red LEDs to indicate status of Neutral Ground protection When the LEDs turn red an audible alarm will...

Page 10: ... the display 3 Remove the two phillips head screws that hold the display 4 Rotate the display to the desired position Be careful not to overstress the display ribbon cable 5 Place the display back onto the SPD enclosure Again be careful not to overstress or crimp the ribbon cable 6 Replace the two phillips head screws Tighten screws to 1 35 Nm 12 in lbs 7 Restore power to the unit 3 3 IEC Approved...

Page 11: ...V Significant surge event Replace SPD Replace SPD with correct voltage model Check electrical system for TOV sources correct replace SPD Replace SPD One of the display Red LEDs is ON Audible Alarm is OFF Audible Alarm Silence button has been depressed and Alarm is silenced Normal operation If power is cycled and a fault condition still exists the Audible Alarm will reactivate All Green and Red LED...

Page 12: ...and 480D Basic voltage codes 600Y and 600D voltage codes 0 6W 1 7W 2 1W Protection modes Single split phase L N L G N G L L Single phase L N L G N G Three phase delta L G L L Three phase Wye L N L G N G L L Three phase high leg delta L N L G N G L L Maximum continuous operating voltage MCOV 208Y 220Y 240S 240D and 240H voltage codes 150 L N 150 L G 150 N G 300 L L 230L 400Y and 480Y voltage codes ...

Page 13: ...ate Protection Status of the N G Mode on units with a Neutral Wire Audible alarm with Silence button Form C Relay Contact EMI RFI filtering Providing up to 50dB of Noise Attenuation from 10kHz to 100Mhz Surge Counter with Reset Button Application Suffix Options Sidemount Units K NEMA 1 Enclosure L NEMA 1 Flushmount Enclosure Available in 50 200kA Ratings Only M NEMA 1 Enclosure With Internal Disco...

Page 14: ...ithin said term determined by Eaton to be defec tive The giving of or failure to give any advice or recommenda tions by Eaton shall not constitute any warranty by or impose any liability upon Eaton The foregoing constitutes the sole and exclusive liability of Eaton AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY FITNESS FOR PURPOSE SOLD DESCR...

Page 15: ...Instruction Manual IM01005031E Rev 6 Effective January 2019 Eaton www eaton com 15 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Notes ...

Page 16: ...and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATIO...

Reviews: