Section 1: Introduction

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual

   MN013001EN   May 2015   www.eaton.com

Figure 2A .  Series NRX Type RF - Frame Cassette Catalog Numbering System .

NF Cassette Catalog Numbering System

Position 1-2

Cassette Family and Breaker Frame

NQ

UL 1066 N-Frame

NY

UL 489 N-Frame

NG

IEC 60947-2 N-Frame - Global 

NA

IEC 60947-2 N-Frame - China

Position 3-4

Continuous Ampere Range

08

800 A (UL 1066)

12

800 - 1200 A (UL 489)

16

630 - 1600 A (IEC)

Position 5

Poles, Phasing (Facing Front of Breaker)

3

3-pole, ABC

4

4-pole, NABC

Position 6

Load Terminal Connections

F

With Flat Tapped Pads Only

G

With Vertical/Horizontal Bus Adaptor Kit (Short Style)

H

With Front Connected Kit

N

No Flat Tapped Pads or Cassette Stabs Inter Unit Only)

Position 7

Arc Hood

A

Arc Hood Installed (Default)

Breaker Overview

Figures 3 through 6 highlight the main components that 

make up a Series NRX breaker .

Drawout Breaker and Cassette

A drawout circuit breaker is used in combination with a dra-

wout cassette (Figures 3 and 4) .  Mounted on the drawout 

breaker are the primary finger clusters and levering mecha-

nism .  These components are located on the breaker to 

allow Users easy access when performing product inspec-

tion or maintenance .  The cassette provides all the neces-

sary drawout circuit breaker interfaces, including primary 

and secondary connections .  Standard flat terminal pads 

on the rear of the cassette provide for a variety of primary 

connection configurations .  Optional primary adapters are 

available for front and rear bus or cable connections .  For 

specific details and mounting instructions for primary adapt-

ers, refer to www .Eaton .com/seriesnrx .
Refer to Section 5 for mounting and installation dimensional 

information .  Electronic files of dimensional drawings for 

customer use are available for download at www .eaton .

com/seriesnrx .

Position 8

Door Frame Gasket and Rejection Kits

B

Door Kit Included (Default)

Position 9

TOC Switches (Truck Operated Cell)

N

Not Included (Default)

Position 10

Shutters

N

Not Included (Default)

S

Included

Position 11

Secondary Contact Terminals Installed

N

None

F

Full Complement

B

Defined by Breaker

C

Common Options

Position 12

Future Use

N

None

Position 13

Future Use

N

None

Position 14

Cassette Shipping

C

Cassette Only

B

Breaker Shipped in Cassette

Fixed Circuit Breaker

A fixed circuit breaker is rigidly mounted in its structure with 

no drawout feature .  The circuit breaker is available in front 

and rear-connected configurations (Figure 5) .
The breaker can be mounted on a suitable horizontal mount-

ing surface using left and right-side mounting feet .  A stan-

dard fixed circuit breaker is supplied with flat primary termi-

nal pads on the rear of the breaker that will accommodate a 

variety of primary connection configurations .

Positions

 

1 2 3 4 5 6 7 8 

9  10  11  12 13 14  15 16  17 18  19 20

Summary of Contents for Series NRX

Page 1: ...aker Instruction Manual Instruction Manual MN013001EN Instructions Apply to Type NF Frame Series NRX ANSI UL1066 UL489 IEC IZMX16 Typical Drawout Circuit Breaker and Cassette Typical Fixed Circuit Bre...

Page 2: ...the Drawout Circuit Breaker 14 Rejection Interlocks 15 Circuit Breaker Positioning 15 Installing Fixed Circuit Breaker 17 Operating Mechanism 18 SECTION 3 BREAKER GENERAL OPERATION CIRCUIT BREAKER DES...

Page 3: ...lease SR 25 Latch Check Switch LCS 25 Motor Operator 25 Mechanical Devices 25 SECTION 5 DIMENSIONAL DRAWINGS FOR INSTALLATION OF DRAWOUT CIRCUIT BREAKERS 27 SECTION 6 DIMENSIONAL DRAWINGS FOR INSTALLA...

Page 4: ...ply could result in the cassette tipping for ward resulting in equipment damage and or bodily injury CAUTION Do not store equipment on its back This could result in equipment damage CAUTION It is impo...

Page 5: ...nce of this equipment the following prac tices must be followed 1 Only qualified electrical personnel familiar with the equipment its operation and the associated hazards should be permitted to work o...

Page 6: ...Figure 1 Become familiar with the nameplate Figure 1 Series NRX Nameplate Location NAS6163W Air Circuit Breaker Frame Type NF 1600 Ampere Frame 3 Pole 50 60 Hz Interrupting Ratings RMS Symetrical Amp...

Page 7: ...Hz capability LSI ZSI W Modbus 2Q LSI ZSI W Modbus ARMS 2R LSIG A ZSI W Modbus 2S LSIG A ZSI W Modbus ARMS 2T LSI ZSI W Modbus 2V LSI ZSI W Modbus ARMS 2W LSIG A ZSI W Modbus 2X LSIG A ZSI W Modbus AR...

Page 8: ...ond Shunt Trip N None A 110 125 Vac dc UVR R 208 240 Vac dc UVR L 24 Vdc UVR H 48 Vdc UVR S 60 Vdc UVR 1 110 127 Vac dc Second Shunt Trip 2 208 240 Vac dc Second Shunt Trip 4 24 Vdc Second Shunt Trip...

Page 9: ...Metal Counter Provided 5 PB Covers Metal Metal Safe Off No Counter 6 PB Covers Metal Metal Safe Off Counter Provided Position 19 Drawout Breaker Shipping Fixed Breaker Terminals Door Frame Kit D Drawo...

Page 10: ...es including primary and secondary connections Standard flat terminal pads on the rear of the cassette provide for a variety of primary connection configurations Optional primary adapters are availabl...

Page 11: ...www eaton com Figure 3 Typical NRX Type NF Drawout Circuit Breaker Front and Rear Views Note N Refer to Figure 6 for more visual details of front cover 1 Arc Chute Cover 2 Primary Shroud 3 Lifting Ha...

Page 12: ...d Rear Views 1 Drawout Extension Rail 2 Stationary Primary Contacts 3 Interlock Plate Pins 4 Grounding Earthing Bar 5 Safety Shutters Open 6 Hand Lifting Indentation 7 Gas Ventilation Opening 8 Second...

Page 13: ...e NF Fixed Circuit Breaker Rear Connected Type Note N Refer to Figure 6 for more visual details of front cover 1 Arc Hood Baffle 2 Arc Hood 3 Secondary Contacts 4 Front Cover 5 Secondary Wiring Contac...

Page 14: ...4 Nameplate 5 Manual ON 6 Operations Counter 7 Position Indicator 8 Levering Access Door 9 Frame Rating Module 10 FRM Battery Cover 11 Manual OFF 12 USB and Aux Power Ports 13 Pop out Trip Flag 14 Tr...

Page 15: ...at top of indicator is partially full or totally full of blue beads Transport was not in keeping with instructions breaker con tainer was tilted or overturned Check breaker closely for dam age Triang...

Reviews: