Section 2: Receiving, Handling, and Installation

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual

   MN013001EN   May 2015   www.eaton.com

Section 2: Receiving, Handling, and Installation

Suggested Tools

Flat-blade and Phillips head screwdrivers

3/8-inch levering tool or extension/ratchet

3 mm Allen head screwdriver

1/2 inch socket and ratchet or 1/2 inch wrench

Circuit Breaker Unpacking and Inspection

Inspect the shipping container(s) for obvious signs of exter-

nal damage .  Record any observed damage for reporting to 

the transportation carrier and Eaton .  All reports and claims 

should be as specific as possible and include the order num-

ber and other applicable nameplate information .

ote:

N

The outside of the circuit breakers shipping container 

includes a transport “Tip-N-Tell” indicator alerting the 

receiver as to whether or not the shipping container 

was transported and handled in the required manner . 

Refer to Table 1 for details about the indicator before 

removing the circuit breaker from its container .

Table 1 .  Transport Indicator .

Triangle at top of indicator is 

partially full or totally full of blue 

beads.
•  Transport was not in keeping 

with instructions (breaker con-

tainer was tilted or overturned).

•  Check breaker closely for dam-

age.

Triangle at top of indicator has no 

blue beads in it. 

•  Breaker container was not tilted or 

overturned during transport.

Triangle

Blue Beads

When ready to inspect and/or install a Series NRX circuit 

breaker, proceed with the following steps:

Step 1: 

Carefully open the container and remove all packing/

shipping material and documentation .

Figure 7 .  Step 1 .

ote:

N

Also follow Step 1 when handling a separately 

shipped drawout cassette .

Step 2: 

Save all packing/shipping material and documenta-

tion for future shipments or breaker storage purposes .

Step 3: 

Move the breaker to a convenient place for closer 

examination .  Drawout breakers are provided with a lifting 

handle on both sides to assist lifting .  Repeat for a drawout 

cassette .  The cassette is provided with a lifting indentation 

on each side . 

Use an appropriate device to lift the breaker or cassette 

(Table 2) .  If one is not available, it is recommended 

that a minimum of two people be used to lift/move a 

breaker or cassette .

ote:

N

Refer to Table 2 for additional precautions and lifting 

procedures .

Figure 8 .  Step 3 .

Lifting 

Handle

Lifting 

Area

Summary of Contents for Series NRX

Page 1: ...aker Instruction Manual Instruction Manual MN013001EN Instructions Apply to Type NF Frame Series NRX ANSI UL1066 UL489 IEC IZMX16 Typical Drawout Circuit Breaker and Cassette Typical Fixed Circuit Bre...

Page 2: ...the Drawout Circuit Breaker 14 Rejection Interlocks 15 Circuit Breaker Positioning 15 Installing Fixed Circuit Breaker 17 Operating Mechanism 18 SECTION 3 BREAKER GENERAL OPERATION CIRCUIT BREAKER DES...

Page 3: ...lease SR 25 Latch Check Switch LCS 25 Motor Operator 25 Mechanical Devices 25 SECTION 5 DIMENSIONAL DRAWINGS FOR INSTALLATION OF DRAWOUT CIRCUIT BREAKERS 27 SECTION 6 DIMENSIONAL DRAWINGS FOR INSTALLA...

Page 4: ...ply could result in the cassette tipping for ward resulting in equipment damage and or bodily injury CAUTION Do not store equipment on its back This could result in equipment damage CAUTION It is impo...

Page 5: ...nce of this equipment the following prac tices must be followed 1 Only qualified electrical personnel familiar with the equipment its operation and the associated hazards should be permitted to work o...

Page 6: ...Figure 1 Become familiar with the nameplate Figure 1 Series NRX Nameplate Location NAS6163W Air Circuit Breaker Frame Type NF 1600 Ampere Frame 3 Pole 50 60 Hz Interrupting Ratings RMS Symetrical Amp...

Page 7: ...Hz capability LSI ZSI W Modbus 2Q LSI ZSI W Modbus ARMS 2R LSIG A ZSI W Modbus 2S LSIG A ZSI W Modbus ARMS 2T LSI ZSI W Modbus 2V LSI ZSI W Modbus ARMS 2W LSIG A ZSI W Modbus 2X LSIG A ZSI W Modbus AR...

Page 8: ...ond Shunt Trip N None A 110 125 Vac dc UVR R 208 240 Vac dc UVR L 24 Vdc UVR H 48 Vdc UVR S 60 Vdc UVR 1 110 127 Vac dc Second Shunt Trip 2 208 240 Vac dc Second Shunt Trip 4 24 Vdc Second Shunt Trip...

Page 9: ...Metal Counter Provided 5 PB Covers Metal Metal Safe Off No Counter 6 PB Covers Metal Metal Safe Off Counter Provided Position 19 Drawout Breaker Shipping Fixed Breaker Terminals Door Frame Kit D Drawo...

Page 10: ...es including primary and secondary connections Standard flat terminal pads on the rear of the cassette provide for a variety of primary connection configurations Optional primary adapters are availabl...

Page 11: ...www eaton com Figure 3 Typical NRX Type NF Drawout Circuit Breaker Front and Rear Views Note N Refer to Figure 6 for more visual details of front cover 1 Arc Chute Cover 2 Primary Shroud 3 Lifting Ha...

Page 12: ...d Rear Views 1 Drawout Extension Rail 2 Stationary Primary Contacts 3 Interlock Plate Pins 4 Grounding Earthing Bar 5 Safety Shutters Open 6 Hand Lifting Indentation 7 Gas Ventilation Opening 8 Second...

Page 13: ...e NF Fixed Circuit Breaker Rear Connected Type Note N Refer to Figure 6 for more visual details of front cover 1 Arc Hood Baffle 2 Arc Hood 3 Secondary Contacts 4 Front Cover 5 Secondary Wiring Contac...

Page 14: ...4 Nameplate 5 Manual ON 6 Operations Counter 7 Position Indicator 8 Levering Access Door 9 Frame Rating Module 10 FRM Battery Cover 11 Manual OFF 12 USB and Aux Power Ports 13 Pop out Trip Flag 14 Tr...

Page 15: ...at top of indicator is partially full or totally full of blue beads Transport was not in keeping with instructions breaker con tainer was tilted or overturned Check breaker closely for dam age Triang...

Reviews: