Start-Up
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
33
Step 2 - Systems without batteries connected
Ignore this Step if the EPS2/EPS5 system has batteries connected.
1
In the SC200 or SC100 configuration file, set the battery capacity to zero
(to indicate no batteries are connected):
•
Either:
On SC100 go to: Menu > Configuration > System > Edit > Battery
Capacity >Edit, or
On SC200 go to: Battery > Battery > Battery Capacity.
•
Set Battery Capacity to zero.
2
Disable the Temperature Compensation control process (this is only
required when batteries are connected):
•
Either:
On the SC100 go to: Menu > Configuration > Temp Compensation >
Edit, or
On SC200 go to: Control Processes > Temperature Compensation >
Enabled.
•
Select
Disable
.
3
Change Float Voltage (dc output voltage) if required:
•
If required, the Float Voltage (dc output voltage) can be adjusted
within the Output Voltage range in the Specifications on page
.
•
Refer to the SC200 or SC100 system controller System Controller
Operation Handbook for details on how to adjust the Float Voltage.
•
Also adjust the alarm voltage settings (Low Load, Low Float, High
Float and High Load).
Step 3 - Setup communications (if required)
For an overview of communications options see External Communications on
page
.
To configure the communications settings refer to Communications Options in
the System Controller Operation Handbook (see Related Information on page
Procedure complete