Instructional Leaflet 

IL03902001E

Effective February 2011

S811 quick installation guide

 

 

eaton corporation

 www.eaton.com

FLa setting calculation

The FLA setting is a function of the product of the motor nameplate 

full load amperes (FLA) and a multiplier from the service factor  

multiplier (SF) in 

Table 2

 below.

FLA setting = Motor FLA x SF multiplier
For example, an S811R13N3S with a 100A, 1.15 service factor motor 

should have an FLA setting of 115 (100 x 1.15).
Please refer to sizing charts in product user manual, MN03902002E, 

or call 877-ETN-CARE (386-2273) for assistance in sizing a soft  

starter for specific applications.

Table 2.  FLA Ranges

Frame  

Size

FLa current  

range

catalog  

number

N (65 mm)

11–37

S811N37N3S

20–66

S811N66N3S

R (110 mm)

32–105

S811R10N3S

42–135

S811R13N3S

T (200 mm)

56–180

S811T18N3S, S811T18V3S

75–240

S811T24N3S, S811T24V3S

95–304

S811T30N3S, S811T30V3S

U (200 mm)

112–360

S811U36N3S

131–420

S811U42N3S

156–500 

a

S811U50N3S

V (290 mm)

112–360

S811V36N3S, S811V36V3S

131–420

S811N42N3S, S811V42V3S

156–500

S811N50N3S, S811V50V3S

203–650

S811N65N3S, S811V65V3S

225–720

S811N72N3S, S811V72V3S

265–850

S811N85N3S, S811V85V3S

310–1000

S811V10N3S

500A rating does not have IEC certification.

Wiring and control check list for operating 

through the control terminal block

A jumper is installed between terminals P and 1 for two-wire  

control (e.g., RUN/STOP toggle switch or PLC control)
24V power supply meets minimum requirements (55 watt  

steady-state, 240 watt inrush for 180 ms, 30 Vdc maximum.)
Control power wire for the positive and negative terminals  

is 14 AWG or larger
Control wire length less than 100 feet
24V is supplied to pin 3 on the control terminal block if controlling 

through these terminals is desired

power wiring check list

24 Vdc control voltage will be applied to terminal P
Phase sequence is correct (ABC); otherwise, soft starter will  

trip on phase reversal
If output isolation contactor is used, it cannot open until the  

soft starter stops to prevent a low current trip

After completing the above, apply line power, apply 24 Vdc control 

voltage, and then initiate start signal to energize motor.

check list—settings—special applications

You may improve performance if operating on generator power  

by setting the kick start time to 2 seconds and kick start torque  

to half the value of the initial torque setting. This creates a step  

loading effect of the generator, allowing the governor to regulate  

the power demand of starting larger motors.

troubleshooting

For additional setting details, refer to the S811 User Manual  

MN03902002E available at www.eaton.com/electrical.  

For technical questions, please contact EatonCare at  

877-ETN-CARE (386-2273).