Appendix G—Modbus Register Map
S811+ Soft Starter
MN03900001E—November 2012
71
Motor Control Output
Configuration
S811 output#1 cfg
S811 output#2 cfg
Network output#1 cfg
Network output#2 cfg
2
2
2
2
633
634
635
636
R/W
R/W
R/W
R/W
UINT16
UINT16
UINT16
UINT16
0 = No function
1 = Faulted
2 = Not Faulted
3 = Bypass
4 = Not Bypass
5 = Motor Energized
6 = Motor Not Energized
7 = Warning
8 = Not Warning
9 = Custom Codes
10 = Not Custom Codes
Motor Control Output Custom
Fault Configuration
2
2
2
637
638
639
R/W
R/W
R/W
UINT16
UINT16
UINT16
Custom fault code#1
Custom fault code#2
Custom fault code#3
Fault Reset Mode
1
640
R/W
UINT8
0 = Manual reset
1 = Auto reset
2 = Power on reset
Auto Reset Delay Time
2
641
R/W
UINT16
0.1–600.0 sec (in 0.1 sec)
Auto Reset Number of Reset
Attempts Limit
2
642
R/W
UINT16
0–10000
Overload Fault Enable
1
643
R/W
UINT8
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Overload During Start
Enable
1
644
R/W
UINT8
1 = enable
0 = disable
Phase Reversal Fault Enable
1
645
R/W
UINT8
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Undercurrent Fault
(Warning) Trip Enable
1
646
R/W
UINT8
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Undercurrent Fault Trip
Level (% FLA)
1
647
R/W
UINT8
0–100%
Motor Undercurrent Fault
Duration
2
648
R/W
UINT16
0.1–60.0 sec (in 0.1 sec)
Motor Jam Fault Enable
1
649
R/W
UINT8
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Stall Fault Enable
1
650
R/W
UINT8
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Phase Loss Fault Enable
1
651
R/W
UINT8
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Phase Loss Trip Level
1
652
R/W
UINT8
1–100%
Motor Phase Loss Duration
2
653
R/W
UINT16
0.1–60.0 sec (in 0.1 sec)
Motor Phase Imbalance Fault
Enable
1
654
R/W
UINT8
0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Motor Phase Imbalance Fault
Level
1
655
R/W
UINT8
1–100%
Motor Phase Imbalance Fault
Duration
2
656
R/W
UINT16
0.1–60.0 sec (in 0.1 sec)
Register Map, continued
Parameter
Data
Length
Modbus
Register
Number
Read/Write
Data
Type
Description