
Appendix G—Modbus Register Map
68
S811+ Soft Starter
MN03900001E—November 2012
Scaled Average Three Phase
Currents in amps—Pole
2
352
R
UINT16
Scaled Average pole current in Amps
Scaled Three Phase Currents in
amps—Pole
2
353
R
UINT16
L1 RMS pole current in Amps
2
354
R
UINT16
L2 RMS pole current in Amps
2
355
R
UINT16
L3 RMS pole current in Amps
Scaled Average Three Phase
Currents in deciamps—Pole
2
356
R
UINT16
Scaled Average pole current in 0.1 Amps
Scaled Three Phase Currents in
deciamps—Pole
2
357
R
UINT16
L1 RMS pole current in 0.1 Amps
2
358
R
UINT16
L2 RMS pole current in 0.1 Amps
2
359
R
UINT16
L3 RMS pole current in 0.1Amps
Power Factor
2
360
R
SINT16
0 to 1.0000 (in 0.0001)
Integer Average Three Phase Real
Power kW
2
361
R
UINT16
Average Real Power (kW)
Power Device Pole
Temperature
2
362
R
SINT16
L1 pole temp in 0.1°C
2
363
R
SINT16
L2 pole temp in 0.1°C
2
364
R
SINT16
L3 pole temp in 0.1°C
DC Control Voltage
2
365
R
UINT16
DC voltage reported in 0.001V
Device Temperature in Degrees C 2
366
R
SINT16
Device temp in 0.1°C
Auto Reset Count
2
367
R
UINT16
# of times S811+ has been auto reset
Line Frequency
2
368
R
UINT16
Line Frequency (in 0.01Hz)
Line Phase Sequence
1
369
R
UINT8
0x01—ABC Phase sequence
0x02—ACB Phase sequence
Fault List
(Fault/Warning codes will be
repeated in the list)
2
370
R
UINT16
Latest Fault/Warning code
2
371
R
UINT16
2nd Latest Fault/Warning code
2
372
R
UINT16
3rd Latest Fault/Warning code
2
373
R
UINT16
4th Latest Fault/Warning code
2
374
R
UINT16
5th Latest Fault/Warning code
2
375
R
UINT16
6th Latest Fault/Warning code
2
376
R
UINT16
7th Latest Fault/Warning code
2
377
R
UINT16
8th Latest Fault/Warning code
2
378
R
UINT16
9th Latest Fault/Warning code
2
379
R
UINT16
10th Latest Fault/Warning code
Application Status
2
380
R
UINT16
Applications status (present fault)
Motor RUN1input level sense
enable
1
381
R
UINT8 0x00—edge
sense
0x01—level sense
Modbus Motor Control (3-Wire)
1
500
R/W
UINT8
bit
0
1
2
3
4
5
6
7
Description
Run1
Run2
Permissive
Fault Reset
reserved
reserved
reserved
Ramp2 enable
Register Map, continued
Parameter
Data
Length
Modbus
Register
Number
Read/Write
Data
Type
Description