Roughneck™

 

(non-EX) 

multi-pin connector

Installation & maintenance information

IF 1688

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

Section 1: Installation Instructions for Multi-pin Male Plugs

To avoid electrical shock or electrocution, if any parts of the 

plug or receptacle appear to be missing, broken or show 

signs of damage, DISCONTINUE USE IMMEDIATELY.  

Replace with the proper replacement part(s) before 

continuing service.

WARNING

SHOCK HAZARD

To avoid electrical shock or electrocution, electrical power

supply must be OFF before and during installation and

maintenance.  Installation and maintenance procedure must

be performed by a trained and competent electrician.

To avoid electrical shock or electrocution, connectors with 

male pins must not be used as the power source, as the 

user may come in contact with energized contacts or other 

components.

A. To disassemble male plug:

1. 

Place cable adapter body (1) in rubber or aluminum 

jawed vice.  Unscrew male skirt (2) (left hand thread) 

from cable adapter (1), keeping environmental cover (3) 

on male skirt (2).  

2. 

Remove cable adapter body (1) from vice and place male 

skirt (2) in vice, clamping onto environmental cover (3) 

with warning label facing down.

3. 

Unscrew coupling nut (4) from environmental cover (3).

WARNING

SHOCK HAZARD

WARNING

SHOCK HAZARD

B. To connect cable to male plug:

1. 

Thread cable through mechanical clamp (9) or 

basketweave (8), bushing (7) then cable adapter (1) then 

coupling nut (4). Allow to rest down cable out of way. 

2. 

Prepare cable and individual conductors following 

directions from Section 6.

3. 

Terminate conductors onto pins per Section 6.

4. 

Confirm resilient insert (6) (red) is firmly in place within 

the male skirt (2). 

5. 

Locate pin location 1 on the insert and press desired 

pin into insert.  Follow pin insertion instructions from 

Section 7.

6. 

Continue to populate remaining pin locations on insert 

with pins.  WARNING: ALL INSERT LOCATIONS MUST 

BE FULLY POPULATED WITH PINS. 

C. To re-assemble male plug: 

1. 

Thread coupling nut (4) onto environmental cover 

(3).

2. 

Thread cable adapter (1) (left hand thread) onto 

male skirt (2) and tighten to torque value found 

on Table 3.  Verify male skirt (2) is wrenched fully 

to the shoulder of the cable adapter (1) to ensure 

environmental integrity.

3. 

Screw basketweave (8) or mechanical clamp (9) 

onto the end of the cable adapter (1). Screw it 

down tight enough to squeeze the busing firmly 

against the cable. While doing this, push in on the 

cable to prevent strain on the wire terminals. 

4. 

Fully tighten with wrench.

5. 

If using mechanical clamp, tighten cord grip screws 

to torque found on Table 3.

9. Mechanical Clamp

7. Bushing

1. Cable Adapter

4. Coupling Nut

2. Male Skirt

3. Environmental 

    Cover

6. Resilient Insert

8.Basket 

Weave

Section 2: Installation Instructions for Multi-pin Female Inline and Square Flange 

Receptacle

A. To disassemble female inline receptacle:

1. 

Place cable adapter (1) in rubber or aluminum jawed vice.  

Unscrew female skirt (2) (left hand thread) from cable 

adapter (1), keeping environmental cover (3) on female 

skirt (2).  

2. 

Remove cable adapter (1) from vice and place female skirt 

(2) in vice, clamping onto environmental cover (3) with 

warning label facing down.

B. To connect cable to female inline receptacle: 

1. 

Thread cable through mechanical clamp (9) or basketweave 

(8), bushing (7) and cable adapter (1). Allow to rest down 

the cable out of way. 

2. 

Prepare cable and individual conductors following 

directions from Section 6.  

3. 

Terminate conductors onto pins per Section 6.

4. 

Confirm resilient insert (6) (green) is firmly in place.

5. 

Locate pin location 1 on the insert and press desired 

           pin into insert.  Follow pin insertion instructions from 

           Section 7.

C. To re-assemble female inline receptacle: 

1. 

Thread cable adapter (1) (left hand thread) onto female 

skirt (2) and tighten to torque value found in Table 3.  

Verify female skirt (2) is wrenched fully to the shoulder 

of cable adapter (1) to ensure environmental integrity.

2. 

Torque mechanical clamp (9) or basketweave (8) to 

cable adapter (1) per torque value found in Table 3. 

3. 

Screw basketweave (8) or mechanical clamp (9) onto 

the end of the cable adapter (1). Screw it down tight 

enough to squeeze the bushing firmly against the 

cable. While doing this, push in on the cable to prevent 

strain on the wire terminals. 

4. 

Fully tighten with wrench.

5. 

If using mechanical clamp, tighten cord grip screws to 

torque found on Table 3.

7. Bushing

1. Cable Adapter

2. Female 

Skirt

3. Environmental 

    Cover

9. Mechanical Clamp

6. Resilient Insert

8.Basket 

Weave

1. Insert Clamp Nut

2. Female Square 

    Flange Skirt

3. Environmental Cover

Section 3: Installation Instructions for Panel Mount Receptacle 

A. To disassemble female panel mount receptacle:

1. 

Place female square flange skirt (2) in rubber or 

aluminum jawed vice with top of environmental cover 

(3) facing the floor.  Unscrew insert clamp nut (1) (left 

hand thread) from female square flange skirt (2), keeping 
environmental cover (3) on female square flange skirt (2).  

B. To connect cable to panel mount receptacle:

1. 

Thread cable through insert clamp nut (1) and allow to 

rest further down on the cable out of the way.

2. 

If using multi-conductor cable, refer to Section 2 (step 

B2-B6) for cable installation process. If using single 

conductor cable, refer to Section 4 (step B2-B5) for male 

contact and Section 5 (step B2-B6) for female contact 

installation process.

C. To re-assemble female panel mount receptacle: 

1. 

Thread insert clamp nut (1) (left hand thread) onto 

square flange skirt (2) and tighten to torque value found 

on Table 3.  Verify female square flange skirt (2) is 

wrenched fully to the shoulder of insert clamp nut (1) to 

ensure environmental integrity.

6.       Continue to populate remaining pin 

          locations on insert with pins. WARNING: ALL INSERT 

          LOCATIONS MUST BE FULLY POPULATED WITH 

          PINS.

Note:  

For use with stranded copper wire.

 

Reference Section 9 for maximum heat dissipation calculation, prior to installation.

 

To be sold with Installation Instructions.

Summary of Contents for Roughneck IF 1688

Page 1: ...uare Flange Receptacle A To disassemble female inline receptacle 1 Place cable adapter 1 in rubber or aluminum jawed vice Unscrew female skirt 2 left hand thread from cable adapter 1 keeping environme...

Page 2: ...to prevent strain on the wire terminals 3 Fully tighten wrench 4 If using mechanical clamp tighten cord grip screws to torque found on Table 3 Retaining Clip Brass Washer 7 Bushing 1 Cable Adapter 4...

Page 3: ...m Current and Resistant Values Pin size Max current A Resistance ohms 23 AWG 1 AMP 0 0218 16 AWG 18 AMP 0 0053 13 AWG 26 AMP 0 0028 12 AWG 30 AMP 0 0021 10 AWG 40 AMP 0 0013 8 AWG 55 AMP 0 00086 4 AWG...

Page 4: ...t no 8 CH 2 8250 CH 1265 10 CH 2 8250 CH 1205 12 CH 2 8250 AT 1000 12 16 CH 2 8250 AT 1000 16 IF 1688 08 18 Table 2 External Cable Jacket Strip Length Jacket strip length culti conductor cable Standar...

Page 5: ...anco y coloque el borde hembra 2 en el tornillo de banco sujete por la cubierta protectora 3 con la etiqueta de advertencia hacia abajo B Para conectar un cable al recept culo hembra integrado 1 Pase...

Page 6: ...a torsi n indicada en la Tabla 3 Abrazadera de retenci n Arandela de lat n B Para conectar el conector macho a la cubierta de aislamiento 1 Deslice la malla c nica 8 o la pinza mec nica 9 el adaptador...

Page 7: ...ntactos m ltiples en el armaz n Si usa conductores m ltiples el calor disipado vatios no debe exceder los niveles indicados en la Tabla B La f rmula a continuaci n se puede usar para calcular el calor...

Page 8: ...CH 2 8250 AT 1000 16 IF 1688 08 18 Tabla 2 Longitud de la camisa de cable desprovista Longitud de la camisa desprovista Cable de conductores m ltiples Adaptador Corto Adaptador Largo pulgadas mm pulga...

Page 9: ...7 et l adaptateur de c ble 1 D gagez le c ble de mani re avoir une longueur suffisante pour travailler confortablement 2 Pr parez le c ble et chaque conducteur individuel conform ment aux instruction...

Page 10: ...ironmental Cover 9 Mechanical Clamp 8 Basket Weave 9 Retaining Clip 8 Brass Washer 11 Insulator Housing 7 Male Contact B Pour brancher le contact m le au bo tier isolant faites ceci 1 Faites glisser l...

Page 11: ...rs contacts sont utilis s dans une m me coquille Lorsqu un c ble multipolaire est utilis la chaleur dissip e watts ne devrait pas d passer les valeurs indiqu es dans le tableau B Utilisez la formule c...

Page 12: ...2 16 CH 2 8250 AT 1000 16 IF 1688 08 18 Tableau 2 Longueur de d nudage de la gaine ext rieure du c ble Longueur de d nudage de la gaine ext rieure c ble multipolaire Adaptateur Court Adaptateur Longue...

Reviews: