UL

®

Cautions, Warnings and Instructions

UL

®

File: E253552

UL61800-5-1

CSA C22.2 No 274

USA: ULus

Indicates Investigated to United States Standard UL61800-5-1 - Listed.

Canada: cUL

Indicates Investigated to Canadian Standard CSA 22.2 No.274 - Listed

Electrical ratings

General

– These devices are solid state variable/speed ac drive inverters which

convert a fixed frequency three phase input voltage to a 3-phase, variable

frequency, variable voltage output. The inverter automatically maintains the

required volts-Hz ratio allowing the ac motor to run at its optimum efficiency

and provide constant torque capability through the motor speed range.

– The power conversion equipment provides solid state motor overload protection.

– Over-Current function was evaluated. Maximum current limit is 150 percent

of FLC. The adjustable range is 0 to 150 percent of FLC.

– Drive is provided with solid state short circuit protection circuitry which is

the same throughout the series. Current sensing is accomplished by

monitoring the DC bus and/or all the motor outputs.

– These drives or control units have not been evaluated as providing a safety

or limiting feature.

– The devices use the supplied thermocouple in the IGBT packs to control

thermal functions – 100 % production test used to confirm functionality.

– These devices are for installation in overvoltage category III and

pollution degree 3.

– Auxiliary control outputs intended to drive resistive load.

Short circuit rating

RASP5-…-xxxR (disconnect switch)

Environmental ratings

– Maximum ambient air temperature: 55 °C

– Enclosure type 12

Further specifications and information

– Use copper conductors only

– 75 °C wire only

– Integral solid state short circuit protection does not provide branch circuit

protection. Branch circuit protection must be provided in accordance with

the National Electrical Code and any additional local codes or the equivalent.

Model – 400 V Range

Input

Output

(3-phase)

(3-phase)

Frame Size

Model number

FLA

FLA

Power

kW

Power

HP

1A

RASP5-2…

2.4

2.4

0.75

1.0

1A

RASP5-3…

3.3

3.3

1.1

1.5

1A

RASP5-4…

4.3

4.3

1.5

2.0

1A

RASP5-5…

5.6

5.6

2.2

3.0

1B

RASP5-6…

6.8

6.8

3.0

4.0

1B

RASP5-8…

8.5

8.5

4.0

5.0

Frame size 1A = no external fan fitted.

Frame size 1B = external fan fitted.

Input voltage 380 - 480/277 V AC, 50/60 Hz

Output voltage 20 - 500 V AC, 0 - 500 Hz

Terminals –

All Models

Qty

Maximum ratings

Sensor supply

3

24 V 100 mA

Motor Brake

1

600 mA 400 V

(6 A < 120 ms)

Model

Short circuit rating (kA)
Fuses

(J-Type)

Breakers

(Type C)

…When protected by

100 kA

… Class J fuses

RASP5

10 kA

… Circuit breaker (Type C)

65 kA

… Type E Combination Motor Controller
… Class J fuses

RASP5-…-xxxR

(with repair switch)

10 kA

… Circuit breaker (Type C)
… Type E Combination Motor Controller

NOTICE

Suitable for use on a circuit capable of delivering not more than 100 000 rms

symmetrical amperes, 480 volts maximum. Suitable for motor group

installation. When protected by J class fuses rated 30 A.
Suitable for use on a circuit capable of delivering not more than 65 000 rms

symmetrical amperes, 480 volts maximum. When protected by type E

combination motor controller model PKZM4-32 manufactured by Eaton

rated 480Y/277 V AC 20 HP.
Suitable for use on a circuit capable of delivering not more than 10 000 rms

symmetrical amperes, 480 volts maximum. Suitable for motor group

installation. When protected by a circuit breaker having an interrupting rating

not less than 10 000 rms symmetrical amperes, 480 volts maximum, rated 32 A.

NOTICE

Suitable for use on a circuit capable of delivering not more than 10 000 rms

symmetrical amperes, 480 volts maximum. Suitable for motor group

installation. When Protected by J Class fuses rated 30 A.
Suitable for use on a circuit capable of delivering not more than 10 000 rms

symmetrical amperes, 480 volts maximum. Suitable for motor group

installation. When protected by circuit breaker having an interrupting rating

not less than 10 000 rms symmetrical amperes, 480 volts maximum, rated 32 A.
Suitable for use on a circuit capable of delivering not more than 10 000 rms

symmetrical amperes, 480 volts maximum. When protected by type E

combination motor controller model PKZM4-32 manufactured by Eaton

rated 480Y/277 V AC 20 HP.

WARNING

The opening of the branch-circuit protective device may be an

indication that a fault has been interrupted. To reduce the risk of fire

or electric shock, current-carrying parts and other components of the

controller should be examined and replaced if damaged.

ATTENTION

THE OPENING OF THE BRANCH-CIRCUIT PROTECTIVE DEVICE

MAY BE AN INDICATION THAT A FAULT HAS BEEN INTERRUPTED.

TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, CURRENT-

CARRYING PARTS AND OTHER COMPONENTS OF THE CONTROLLER

SHOULD BE EXAMINED AND REPLACED IF DAMAGED. IF BURNOUT

OF THE CURRENT ELEMENT OF AN OVERLOAD RELAY OCCURS,

THE COMPLETE OVERLOAD RELAY MUST BE REPLACED.

Summary of Contents for RASP5 EIP Series

Page 1: ...z v bu T l k aprakst tos darbus dr kst veikt tikai elektrospeci listi un darbam ar elektrotehnisk m iek rt m instru t s personas Pavojus gyvybei d l elektros srov s Tik elektrikai ir elektrotechnikos...

Page 2: ...control voltage for external motor brakes 2 230 277 V AC control voltage for external motor brakes 4 400 480 V AC control voltage for external motor brakes 2 2 Actuator outputs 4 4 Sensor inputs 2 2...

Page 3: ...6 a 150 mm 5 91 b 100 mm 3 94 c 50 mm 1 97 d 0 TORX 30 IP 1 90 C33 C31 90 2 3 3 Nm 26 55 lb in TORX 30 IP 5 4 173 mm 6 81 110 mm 4 33 110 mm 4 33 220 mm 8 66 245 mm 9 65 270 mm 10 63 6 4 mm 0 25 277 7...

Page 4: ...in 1 3 Nm 11 51 lb in 1 3 Nm 11 51 lb in 1a 1a 110 mm 4 33 110 mm 4 33 245 mm 9 65 110 mm 4 33 110 mm 4 33 245 mm 9 65 1b 1b 245 mm 9 65 173 mm 6 81 4 x M6 245 mm 9 65 173 mm 6 81 4 x M6 2 6 2 mm 0 2...

Page 5: ...la odpojen m nap jen ATENTJE Conecta i doar c nd aparatul nu se afl sub tensiune T HELEPANU hendada ainult pingevabas olekus POZOR Priklju ujte samo u beznaponskom stanju FIGYELEM Csak fesz lts gmente...

Page 6: ...60 V 60 Hz RASP5 2 2 4 A 0 75 kW 1 HP RASP5 4 4 3 A 1 5 kW 2 HP RASP5 5 5 6 A 2 2 kW 3 HP RASP5 8 8 5 A 4 0 kW 5 HP 1 4 6 3 5 8 PE 7 PIN 400 V AC 460 V AC 180 V DC 230 V AC 400 V AC 277 V AC 480 V AC...

Page 7: ...e jun o do motor Kontakt f r motoranslutning Moottorin liitinpistoke P ipojovac z str ka motoru Mootori henduspistik Motorcsatlakoz dug Motora savieno anas spraudnis Variklio jungiamasis ki tukas Przy...

Page 8: ...xxR RASP5 xxx1 RASP5 xxx2 RASP5 xxx4 M 3 6 4 B1 B2 1 3 180 V DC L1 L3 1 4 L1 N 230 277 V AC 0 6 A M 3 6 4 B1 B2 1 3 400 480 V AC 0 6 A L1 L3 M 3 6 4 B1 B2 0 OFF I ON 5 mm 2 x 0 20 2 x 1 3 4 2 11 12 PE...

Page 9: ...b in 1 2 3 0 V 4 24 V 5 F 4 M F 3 1 3 2 4 5 ACHTUNG Hohe Temperatur K hlk rper nicht ber hren WARNING HOT SURFACE Do not touch the heat sink f 100 mm f 3 94 b a a b a b M 3h 20 m 65 6 ft 1 2 NS P1 S P...

Page 10: ...mA en de fr es it zh ru nl da el pt sv fi cs et hu lv lt pl sl sk bg ro hr tr uk ar FAN STO ACT Q1 2 I3 SEN I1 I3 I1 Q2 Q1 P2 A 24V I4 SEN I2 I4 I2 P2 S P2 P1 A P1 S P1 NS MS FLT PWR 1 TD 2 RD 3 TD 4...

Page 11: ...Y OLED DX KEY LED2 DX COM STICK3 KIT en de fr es it zh ru nl da el pt sv fi cs et hu lv lt pl sl sk bg ro hr tr uk ar FAN STO ACT Q1 2 I3 SEN I1 I3 I1 Q2 Q1 P2 A 24V I4 SEN I2 I4 I2 P2 S P2 P1 A P1 S...

Page 12: ...ontrolo externa 24 V DC Extern styrsp nning 24 V DC Ulkoinen ohjausj nnite 24 V DC Extern dic nap t 24 V DC V line juhtimispinge 24 V DC K ls vez rl fesz lts g 24 V DC r j vad bas spriegums 24 V DC I...

Page 13: ...nci n Safe Torque Off STO con suministro interno STO con alimentazione interna STO STO met interne voeding Sikkert frakoblet moment med intern str mforsyning STO Bin rio de seguran a desligado STO com...

Page 14: ...tor e RASP5 xxxxx1xxx STO f RASP5 xxx1 180 V DC RASP5 xxx2 230 277 V only 24 V RJ 45 0 V M 1 2 3 L1 L2 L3 PE 4 N 1 U V W T1 T2 7 3 PE PE 24 V 160 mA I1 I3 I2 I4 F 24 V 100 mA 0 V 6 4 B1 B2 5 8 M 3 1 2...

Page 15: ...OG X 3GC GR EG R CS S PHE CAAG C GI 5 AC X M H C A A 6 GI C C C C U 9SQ S Q CS S L O HA ID NG H F 6 H I LC G K EG G K A Am GrauenStein 51105 K ln Z2JSBC B D _ _ C P1 HGIA C F I F C X _ C D C G C 1 GC...

Page 16: ...8 8 5 8 5 4 0 5 0 Frame size 1A no external fan fitted Frame size 1B external fan fitted Input voltage 380 480 277 V AC 50 60 Hz Output voltage 20 500 V AC 0 500 Hz Terminals All Models Qty Maximum ra...

Reviews: