4
PXR –PCAM adapter module specifications
ProfibuS (DP) CommuniCation aDaPtEr moDulE
IL120009EN March 2017 www.eaton.com
Table 6. Cyclic data exchange monitoring format 2
byte(s)
Data type Description
resolution
0
Uint8
State 0 (byte 0 of monitoring
format 0,
Table 4
)
1
Uint8
State 1 (byte 0 of monitoring
format 0,
Table 4
)
3..2
Uint16
I
L1
(phase A current)
Amps
5..4
Uint16
I
L2
(phase B current)
Amps
7..6
Uint16
I
L3
(phase C current)
Amps
9..8
Uint16
I
Lmax
(maximum value of I
L1
, I
L2
, I
L3
Amps
11..10
Uint16
I
N
(neutral current)
Amps
13..12
Uint16
V
LL avg
(average line-to-line voltage
Volts
15..14
Int16
cos phi (avg apparent PF)
0.1%
17..16
Uint16
Energy
MWh
Table 7. Cyclic data exchange monitoring format 3
byte(s)
Data type Description
resolution
0
Uint8
State 0 (byte 0 of monitoring
format 0,
Table 4
)
1
Uint8
State 1 (byte 0 of monitoring
format 0,
Table 4
)
3..2
Uint16
I
L1
(phase A current)
Amps
5..4
Uint16
I
L2
(phase B current)
Amps
7..6
Uint16
I
L3
(phase C current)
Amps
9..8
Uint16
I
Lmax
(maximum value of I
L1
, I
L2
, I
L3
)
Amps
11..10
Uint16
I
N
(neutral current)
Amps
13..12
Uint16
V
L1-L2
(V
AB
)
Volts
15..14
Uint16
V
L2-L3
(V
BC
)
Volts
17..16
Uint16
V
L3-L1
(V
CA
)
Volts
19..18
Uint16
V
L1-N
(V
AN
)
Volts
21..20
Uint16
V
L2-N
(V
BN
)
Volts
23..22
Uint16
V
L3-N
(V
CN
)
Volts
25..24
Int16
cos phi (avg apparent PF)
0.1%
27..26
Uint16
Energy
MWh
29..28
Uint16
S
total
(total apparent PF)
kVA
Table 8. Cyclic data exchange monitoring format 4
byte(s)
Data type Description
resolution
0
Uint8
State 0 (byte 0 of monitoring
format 0,
Table 4
)
1
Uint8
State 1 (byte 0 of monitoring
format 0,
Table 4
)
3..2
Uint16
I
L1
(phase A current)
Amps
5..4
Uint16
I
L2
(phase B current)
Amps
7..6
Uint16
I
L3
(phase C current)
Amps
9..8
Uint16
I
Lmax
(maximum value of I
L1
, I
L2
, I
L3
Amps
11..10
Uint16
I
N
(neutral current)
Amps
13..12
Uint16
V
L1-L2
(V
AB
)
Volts
15..14
Uint16
V
L2-L3
(V
BC
)
Volts
Table 8. Cyclic data exchange monitoring format 4
byte(s)
Data type Description
resolution
17..16
Uint16
V
L3-L1
(V
CA
)
Volts
19..18
Uint16
V
L1-N
(V
AN
)
Volts
21..20
Uint16
V
L2-N
(V
BN
)
Volts
23..22
Uint16
V
L3-N
(V
CN
)
Volts
25..24
Int16
cos phi (avg apparent PF)
0.1%
29..26
Uint 32
Energy
kWh
31..30
Uint16
S
total
(total apparent PF)
kVA
Table 9. Cyclic data exchange monitoring format 5
byte(s)
Data type Description
resolution
0
Uint8
State 0 (byte 0 of monitoring
format 0,
Table 4
)
1
Uint8
State 1 (byte 0 of monitoring
format 0,
Table 4
)
3..2
Uint16
I
L1
(phase A current)
Amps
5..4
Uint16
I
L2
(phase B current)
Amps
Cyclic data exchange monitoring format 4
byte(s)
Data type Description
resolution
7..6
Uint16
I
L3
(phase C current)
Amps
9..8
Uint16
I
Lmax
(maximum value of I
L1
, I
L2
, I
L3
)
Amps
11..10
Uint16
I
N
(neutral current)
Amps
13..12
Uint16
V
L1-L2
(V
AB
)
Volts
15..14
Uint16
V
L2-L3
(V
BC
)
Volts
17..16
Uint16
V
L3-L1
(V
CA
)
Volts
19..18
Uint16
V
L1-N
(V
AN
)
Volts
21..20
Uint16
V
L2-N
(V
BN
)
Volts
23..22
Uint16
V
L3-N
(V
CN
)
Volts
25..24
Int16
cos phi (avg apparent PF)
0.1%
29..26
Uint 32
Energy
kWh
31..30
Uint16
S
total
(total apparent PF)
kVA
33..32
Uint16
Digital inputs
bit 0 = DIN0
bit 1 = DIN1
bit 2 = DIN2
bit 3..15 = 0 (not used)