background image

Effective May 2019
Supersedes February 2015

PXBCM-MB-BASIC
PXBCM-MB-ENERGY

Instruction Leaflet 

IL150001EN

Power Xpert Branch Circuit Monitor:

Meter Base - Basic and Energy Code Series

COM reset 

button

Base mounting 

screws #8

LED Indicators

Configuration 

switches

Com1/2 RS485 

Modbus RTU

LAN Ethernet 

RJ45 CAT5+ 

STP

MMP 1-4 Meter 

Module ports

Power Supply Mains Terminal PE/N/L

Base mounting 

screws #8

Figure 1. PXBCM-MB controls, connectors and indicators.

The PXBCM-MB is the data acquisition module/

gateway of the PXBCM system. The PXBCM-

MB aggregates the meter data from up to four 

PXBCM-MMS and PXBCM-MME meter modules. 

You can access the data from all channels (includ-

ing virtual meters) through the RS485 COM1 or 

COM2 Modbus port using the RS-485 RTU proto-

col, or the LAN Modbus TCP connection, or view it 

directly through the onboard web server. 
The Modbus address is set through a pair of 

rotary switches (Address H-L) on the front of the 

PXBCM-MB housing. Indicator lights show device 

status (Status) as well as communications sta-

tus for both LAN Ethernet and COM1 or COM2 

Modbus. A mode switch determines user access 

security levels.
The PXBCM-MB must be housed in an appropriate 

NEMA or UL enclosure that ensures the device 

will remain within its specified environmental 

ranges and provides fire and mechanical protec-

tion. In retrofit panel board applications the MB 

must be mounted in an enclosure external from 

the monitored assembly gear, unless the MB is an 

approved accessory for the panel board.
Each Meter Module has the following LED 

Indicators

• 

COM1 or COM2  Rx/Tx Green/Red LEDs – 

RS485 Modbus 

• 

MMP 1-4 Rx/Tx Green/Red LED – Meter 

Module Port communications

• 

LAN Ethernet LEDs in RJ45 jack

• 

Link Green on = Link Active, blink for TxRx 

• 

10/100 Speed - Amber off/on

• 

Status Green/Red bicolor LED –

• 

Green ~ 1Hz blink – Normal heart beat

• 

Red – Application alarm

• 

Com Status: Green/Red bicolor LED: 

• 

Green on = DHCP,  Green off = Fixed IP 

• 

Red on = communications reset mode 

PXBCM-MB Meter Base 

Specifications

• 

Weight ~ 1 lb

• 

W/H/D: 7.0”(17.6 cm)/6.3”(15.8cm)/2.6”(6.6cm)

• 

Each Meter Base can interface to 1-4 Meter 

Modules  (-MMS &/or –MME) 

• 

Housing NEMA 1, IP20

• 

Pollution Degree 2

• 

Operational Temperature range -20 to +70ºC

• 

Storage Temperature range -45 to +85ºC

• 

Elevation 0-3000m

WARNING!

BE SURE THAT ALL SYSTEM POWER IS OFF WHEN COMMISSION-

ING A PXBCM SYSTEM INCLUDING THE INSTALLATION OF THE 

PXBCM-MB METER BASE AND ASSOCIATED COMPONENTS.

Overview

For use with the Power Xpert Branch Circuit Monitor (PXBCM) Basic and 
Energy Code Series meter bases (MB)

 - 

Both the PXBCM-MB-BASIC meter 

base and PXBCM-MB-ENERGY meter base are designed to be used with 

the PXBCM–MME Meter Module External and/or – MMS Meter Module 

Strip.  The Meter Base (MB) sources power to and collects data from the 

Meter Modules through the Meter Module Ports and Cables.  

• 

PXBCM-MMS-(L/R 9/15/21)-A

 Meter Module Strip

• 

PXBCM-MME-X25-333MV 

Meter Module for External CTs

• 

PXBCM-MME-X21-100MA

 Meter Module for External CTs

• 

PXBCM-MMP-CBLnn/-CBLEnn

 Meter Module Port Cable and Cable 

Extension