Power Xpert Branch Circuit Monitor: 

Meter Base - Basic and Energy Code Series 

  

Instruction Leaflet 

IL150001EN

Effective May 2019

• 

Humidity 5-95% noncondensing

• 

UL file # E185559,  UL Standard UL61010-1 

• 

CNL evaluation to CAN/C22.2 No 1010.1.92

• 

CE mark 

• 

EMC EN61326 – IEC61000-4-X level 3

• 

Emissions conducted and radiated as part of PXBCM system.

• 

FCC part 15 class B 

• 

CISPR 11/22 class B 

External Circuit Connections

• 

Com1/2

 RS485 Modbus Slave RTU:

• 

9600 – 115.2K(default) baud

• 

–D, +D, Com/Shield

• 

Use RS485 cable – 4K’=<19.2Kb,2K’ above

• 

LAN

 Ethernet RJ45 CAT5 10/100 base T

• 

Use STP Cat5+ for full EMC compliance

• 

MMP1-4

 Meter Module ports:

• 

2 pair cable 1 pair power, 2nd coms

• 

Use PXBCM-MMP-CBLnn –CBLEnn cables

• 

Each MMP is separately isolated

• 

Power Supply

 mains 100-277VAC L:N

• 

Up to 347 VAC L:N possible with control power transformer

• 

 +/-10%, CAT III, 47-63 Hz , 6W 

• 

Double insulated 

• 

320VAC Surge filter clamp L:N, L:G, N:G - 

Do not high pot! 

• 

Provide external line fuse or breaker sized to protect wiring 

• 

3 position fixed terminal block 1/2/3 = PE/N/L, supporting 12 

AWG (2.5mm) wire. 

A detailed product identification label is on the left side of each 

Meter Base.  This information can also be viewed through the 

PXBCM web configuration with a browser via the LAN Ethernet port.

Figure 2. Example PXBCM-MB Product ID Label.

The MB may be pow-

ered through a single-

phase connection to 

the panel mains.  The 

power connection 

(marked Power Supply 

on the MB) must be 

equipped with both a 

disconnect switch and 

fuse or breaker to pro-

tect the wire. 

Protective 

earth

Neutral

Fuse block

Line

Disconnect 

switch

Com1 RS485 

Modbus RTU

LAN Ethernet 

RJ45 CAT5+ STP

MMP 1-4 Meter 

Module ports

Figure 3. PXBCM-MB external circuit connections.

Please refer to the PXBCM Install Guide 

IB150003EN for complete system detail: 

www.

eaton.com/pxbcm

Figure 4. Meter Base mounting details.

5.65 in

(143.5 mm)

5.5 in

(139.7 mm)

Com2 RS485 

Modbus RTU