3 Installation
3.6 Installing the fieldbus connection
22
DX-NET-DEVICENET
02/14 MN04012005ZEN
www.eaton.com
3.6.2 Bus termination resistor
The first and last modules on a DeviceNet network must be terminated with
a 120
Ω
bus termination resistor. This resistor needs to be connected
between CAN_H and CAN_L.
Figure 12:Bus termination resistors RT: CAN_H and CAN_L terminals
3.6.3 Max. cable lengths
The maximum bus cable length depends not only on the data rate, but also
on the type of cable being used. The following cable types are permitted:
•
A so-called “Thick Cable”,
•
a so-called “Thin Cable”,
•
a so-called “Flat Cable”,
Table 5: Maximum length for specific DeviceNet cables
0
1
n
. . .
R
T
R
T
Baud rate
Maximum cable length [m]
[Kbit/s]
“Thick Cable”
“Thin Cable”
“Flat Cable”
125
500
100
420
250
250
100
200
500
100
100
100