4 CANopen communication settings
4.7 Parameters
CANopen for DA1, DC1, DE11
09/16 MN040019EN
www.eaton.com
43
2133
P3-07
PID1 Output upper Limit
rw
RUN
1
≙
0.1 %
P3-08 - 1000
U16
2134
P3-08
PID1 Output lower Limit
rw
RUN
1
≙
0.1 %
0- P3-07
U16
2135
P3-09
PID1 Output LimitSelect
rw
RUN
0 - 3
U16
2136
P3-10
PID 1 Feedback 1 Source
rw
RUN
0 - 1
WORD
2137
P3-11
PID1 Error Ramp
rw
RUN
1
≙
0.1 %
0 - 250
U16
2138
P3-12
PID1 Feedback 1 DispScale
rw
RUN
0: disabled
1
≙
0.001
0.000 - 50,000
U16
2139
P3-13
PID1 WakeUpLevel
rw
RUN
1
≙
0.1 %
0 - 1000
U16
–
P3-14
Reserved Parameter
–
–
–
–
–
–
P3-15
Reserved Parameter
–
–
–
–
–
–
P3-16
Reserved Parameter
–
–
–
–
–
–
P3-17
Reserved Parameter
–
–
–
–
–
213E
P3-18
PID1 ResetControl
rw
RUN
1
≙
1
0 - 1
U16
2191
P4-01
Motor Control Mode
rw
STOP
0 - 6
U16
2192
P4-02
Motor Identification
rw
STOP
0 - 1
WORD
2193
P4-03
MSC Kp
rw
RUN
1
≙
0.1 %
1 - 4000
U16
2194
P4-04
MSC Ti
rw
RUN
1
≙
0.001 s
1 - 1000
U16
2195
P4-05
Motor PF
rw
RUN
99
≙
0.99
0.00 / 50 - 99
U16
2196
P4-06
M-Ref Source
rw
RUN
0 - 5
U16
2197
P4-07
M-Max Motoring
rw
RUN
2000
≙
200.0 %
0 - 2000
U16
2198
P4-08
M-Min Motoring
rw
RUN
1
≙
0.1 %
0 % - 150 %
U16
2199
P4-09
M-Max Generative
rw
RUN
1
≙
1 %
0 % - 200 %
U16
219A
P4-10
f-MidV/f
rw
STOP
1
≙
0.1 %
0.0 % - 100.0 %
U16
219B
P4-11
V-MidV/f
rw
RUN
1
≙
0.1 %
0.0 % - 100.0 %
U16
219C
P4-12
T-Memory Enable
rw
RUN
1
≙
1
0 - 1
U16
219D
P4-13
Change Phasesequence
Motor
rw
STOP
0 - 1
21F5
P5-01
PDP-Address
rw
RUN
1
≙
1
1-63
U16
21F6
P5-02
CAN0 Baudrate
rw
RUN
0
≙
125 kbps
1
≙
250 kbps
0 - 3
U16
21F7
P5-03
RS485-0 Baudrate
rw
RUN
0
≙
9.6 kbps
1
≙
19.2 kpbs
0 - 4
U16
21F8
P5-04
RS485-0 ParityType
rw
RUN
0
≙
N-1
1
≙
N-2
0 - 3
U16
21F9
P5-05
Comm Timeout Modbus RTU
rw
RUN
1
≙
0.1 s
0.0 - 5.0
U16
21FA
P5-06
Action@Modbus RTU Fault
rw
RUN
1
≙
1
0 - 3
U16
21FB
P5-07
FieldbusRampControl
rw
RUN
1
≙
1
0 - 1
U16
21FC
P5-08
NETSendPZD4
rw
RUN
1
≙
1
0 - 7
U16
CANOpen
Index
[hex]
Para
meter
Designation
Access
Scaling
Value range
Data
format
rw/
ro
RUN/
STOP
Summary of Contents for PowerXL DA1